TROUBLESHOOTING

8

-

4

TABLE 8-1. BOILER TR

OUBLESHOOTING – Contin

ued

FAULT INDICATION

PROBABL

E CAU

SES

CORRECTI

VE ACTI

O

N

DELAYED

INTERL

OCK OPEN

1.

Delaye

d Interlock Jum

pe

r not

installe

d or re

moved.

2.

Device provin

g swit

ch ho

oked to

interloc

ks

is

not c

losed

1.

Che

ck for a jumpe

r pro

pe

rly installed a

cross the del

ayed

interloc

k terminals

in the I/O box.

2.

If there are 2

external wi

re

s on the

se terminals, che

ck to see if

an end

swit

ch

for a device

su

ch a

s a pu

mp, louver, etc. is tied

thes

e interlock

s.

Ens

ure that t

he device

and or its e

nd

switch

are fun

ctional

. (jumper m

ay be temporaril

y installed to test

interlock)

DI

REC

T

D

R

IVE

SIGNAL FAULT

1.

Dire

ct drive

si

gnal is n

ot prese

nt:

Not yet install

ed.

Wrong pol

arit

y.

Signal defe

ctive at source.

Broken or lo

os

e wi

ring.

2.

Signal is not i

solate

d (floati

ng).

3.

Control Box signal type sel

ection

swit

che

s not

set

fo

r c

or

re

ct

signal

type (voltage or cu

rrent).

1.

Che

ck I/O Box to ensure

si

gnal is h

oo

ke

d up.

Hoo

k up if no

t installed.

If installed, ch

eck pola

rity.

Measure sig

nal level.

Che

ck co

ntin

uity of wiring betwe

en source an

d boile

r.

2.

Che

ck sig

nal

at

sour

ce t

o e

nsu

re it

is isol

at

ed.

3.

Check

D

IP sw

itc

h on PMC board to ens

ure it is

s

et correc

tly for

the type of signal bei

ng se

nt. Ch

ec

k co

nt

rol sig

nal t

ype set

in

Config

uratio

n Menu.

FLAME LOS

S

DU

RI

N

G

IG

N

1.

Burne

r Groun

d Scre

w not i

nstalle

d

or loo

se.

2.

Wo

rn flame d

etector

3.

No spark fro

m

Spark Plug

4.

Defe

ctive Ignition Tran

sformer

5.

Defe

ctive Ignition/Stepper (IGST)

Board

6. Defe

ctive

SSOV

1.

Inspe

ct and i

nstall/retig

hte

n Burne

r Gro

und Scre

w.

2.

Remove and

ins

pec

t the flame detec

tor

for s

igns

of wear.

Repl

ace if nece

ssary.

3.

Clo

se the inte

rnal ga

s valve in

the boiler. Install and a

rc a

spa

rk

igniter out

sid

e the unit.

4.

If there is no

spa

rk,

che

ck

for 120VAC a

t the primary

side of the

ignition tran

sf

orme

r du

ring

the ignition cy

cle.

5.

If 120VAC is

not pres

ent, the

IGST Board in the Control Box

may be defective. Refer fault to

qualified servi

ce pe

rson

nel.

6.

While externa

lly arcing t

he spa

rk

ig

niter, observe

the

open/

clo

se in

dicato

r in the Safety Shut-Off Valve to e

nsu

re it is

openi

ng. If th

e valve does

not open, che

ck fo

r 120VA

C

at the

valve’s

input terminals

. If 120

VAC is

not pres

ent, the I

G

ST

board in the Control Box may be

defective. Refer fault to

qualified servi

ce

pe

rsonn

el.