3 control panel menus, 1 menu processing procedure, Control panel operating procedures – AERCO KC1000 Low NOx Boiler equipped with C-More 2003 User Manual

Page 23

Advertising
background image

CONTROL PANEL OPERATING PROCEDURES

3-3

Table 3-1. Operating Controls, Indicators and Displays -

Continued

ITEM

NO.

CONTROL, INDICATOR

OR DISPLAY

FUNCTION

10

(Cont.)

▲ (Up) Arrow

When in one of the main menu categories (Figure 3-2),
pressing this key will select the displayed menu category. If
the CHANGE key was pressed and the menu item is flashing,
pressing the ▲ arrow key will increment the selected setting.

▼ (Down) Arrow

When in one of the main menu categories (Figure 3-2),
pressing this key will select the displayed menu category. If
the CHANGE key was pressed and the menu item is flashing,
pressing the ▼ (Down) arrow key will increment the selected
setting.

CHANGE

Permits a setting to be changed (edited). When the
CHANGE

key is pressed, the displayed menu item will begin

to flash. Pressing the ▲ or ▼ arrow key when the item is
flashing will increment or decrement the displayed setting.

ENTER

Saves the modified menu information in memory. The
display will stop flashing.

11

AUTO/MAN

Switch

This switch toggles the boiler between the Automatic and
Manual modes of operation. When in the Manual (MAN)
mode, the front panel controls are enabled and the MANUAL
status LED lights.

When in the Automatic (AUTO) mode, the MANUAL status
LED will be off and the front panel controls disabled.

12

FIRE RATE

Bargraph

20 segment red LED bargraph continuously shows the Fire
Rate in 5% increments from 0 to 100%


3.3. CONTROL PANEL MENUS

The Control Panel incorporates an extensive
menu structure which permits the operator to set
up, and configure the unit. The menu structure
consists of four major menu categories as
shown in Figure 3-2. Each of the menus shown,
contain options which permit operating
parameters to be viewed or changed. The
menus are protected by a password to prevent
unauthorized use.

Prior to entering the correct password, the
options contained in the Operating, Setup,
Configuration and Tuning Menu categories can
be viewed. However, with the exception of
Internal Setpoint Temperature (Configuration
Menu), none of the viewable menu options can
be changed.

Once the valid password (159) is entered, the
options listed in the Setup, Configuration and
Tuning menus can be viewed and changed, if
desired.

3.3.1. Menu Processing Procedure

Accessing each menu and option is accom-
plished using the Menu Keys shown in Figure 3-
1. Therefore, it is imperative that you be
thoroughly familiar with the following basic steps
before attempting to perform specific menu
procedures.

1. The Control Panel will normally be in the

Operating Menu and the VFD will display the
current unit status. Pressing the ▲ or ▼
arrow key will display the other available data
items in the Operating Menu.

2. Press the MENU key. The display will show

the Setup Menu which is the next menu
category shown in Figure 3-2. This menu
contains the Password option which must be
entered if other menu options will be
changed.

3. Continue pressing the MENU key until the

desired menu is displayed.