SAFETY DEVICE TESTING

6-5

6.10 PURGE SWITCH OPEN DURING
PURGE

1. Set the unit’s ON/OFF switch to the OFF

position. Place the unit in manual mode and
set the fire rate between 25% and 30%


2. Remove the air/fuel valve cover by rotating

the cover counterclockwise to unlock it and
then pulling it towards you. See Fig. 6.7.


3. Remove one of the two wires from the purge

switch (Fig. 6.8) and start the unit.


4. The unit should begin to start, then shut

down and display PRG SWITCH OPEN
DURING PURGE.


5. Replace the wire on the purge switch and

depress the CLEAR button. The unit should
restart.

Figure 6.7

Air/Fuel Valve Cover Location

6.11 IGNITION SWITCH OPEN DURING
IGNITION

1. Set the unit’s ON/OFF switch to the OFF

position. Place the unit in manual mode and
set the fire rate between 25% and 30%.


2. Remove the air/fuel valve cover (Fig. 6.7) by

rotating the cover counterclockwise to
unlock it then pulling it towards you.


3. Remove one of the two wires from the

ignition switch (Fig. 6.8) and start the unit.


4. The unit should begin to start then shut

down and display IGN SWITCH OPEN
DURING IGNITION.


5. Replace the wire on the ignition switch and

depress the CLEAR button. The unit should
restart.

Figure 6.8

Air/Fuel Valve Purge and Ignition Switch

Locations