INITIAL START-UP

4-8

4.6 OVER TEMPERATURE LIMIT
SWITCH ADJUSTMENTS

There are two Over-Temperature Limit switches
that turn off the unit when the outlet water
temperature becomes too hot. The lower over-
temperature limit switch is adjustable and should
be adjusted 20° to 40°F above the operating
header temperature. The upper over-temper-
ature limit switch is a manual reset device and is
not adjustable. It will shut the unit off if the water
temperature reaches 240°F. DO NOT attempt to
adjust its setpoint.

To adjust the lower over temperature switch limit
switc

h:

1. Remove the wing nut from the top center of

the shell cap. Lift the cap off the shell.

2. The two over-temperature limit switches are

located at the top of the shell (see Fig. 4.6).
Do not adjust the upper switch it has been
factory preset. Adjust the lower switch
between 20° to 40°F higher than the
maximum header temperature the unit may
see.

3. Replace the shell cap and wing nut.

Figure 4.6

Over Temperature Limit Switch Location