APPENDIX A

A-1

BOILER MENU ITEM DESCRIPTIONS

MENU LEVEL & OPTION

DESCRIPTION

OPERATING MENU

Active Setpoint

This is the setpoint temperature to which the
control is operating when operating in the
Constant Setpoint, Remote Setpoint or Outdoor
Reset Mode. When in the Constant Setpoint
Mode, this value is equal to the Internal Setpoint
setting in the Configuration Menu. When in the
Remote Setpoint Mode, this value is the setpoint
equivalent to the remote analog signal supplied to
the unit. When in the Outdoor Reset Mode, this is
the derived value from the charts in Appendix D.

Aux Temp

For monitoring purposes only

Outdoor Temp

Displayed only if an outdoor sensor is installed and
enabled in the Configuration Menu.

Fire Rate In

Indicates desired input fire rate. This will normally
be the same as the fire rate shown on the bar-
graph (fire rate out) when the boiler is operating.

Flame Strength

Displays flame strength from 0 to 100%.

Run Cycles

Displays the total number of run cycles from 0 to
999,999.

Run Hours

Displays total run time of unit in hours from 0 to
999,999.

Fault Log

Displays information on the last 9 faults.