MODULEX EXT 321, 481, 641, 802, 962, 1123 BOILERS

Installation, Operation & Maintenance Manual

Table 5-4: USER Menu

LEVEL

DESCRIPTION

ENTRY

INSTALLATION

Default

Range

ENGLISH

Set language

ENG

CONTRAST

Adjust intensity of display

00

(-20) / (20)

DISPLAY SEL

Select additional display in standard operation

----

SELEC-PROG

Heating circuit 1 or Heating circuit 2

01

(01 ÷ 02)

RETURN

HOT WATER
1-DHW

If the value is 1, the boiler switches on immediatly

00

(01 ÷ 02)

T-DHW 1

Hot water temperature setting in first enable time

140

(50 ÷ 158)

T-DHW 2

Hot water temperature setting in second enable time

140

(50 ÷ 158)

T-DHW 3

Hot water temperature setting in third enable time

140

(50 ÷ 158)

BOB VALUE

Operation without burner (solar or solid fuel integration)

0

(0 ÷ 126)

CIRCL-P-DHW

if the value is 01, the circulation pump runs when the
hot water is enabled, but the circulation program is
disabled.

0

(0 ÷ 1)

ANTILEGION

If the value is 01, every 20th time that heating takes
place or once a week on Saturday at 1:00, the storage
tank is heated up to 149° F

0

(0 ÷ 1)

RETURN

HTG CIRCUIT 1/2

MODE

When setting an alternative oparating mode this only
applies to the assigned heating circuit

-----

T-ROOM DES 1

Room temperature setting in first enable time

68

(41÷105)

T-ROOM DES 2

Room temperature setting in second enable time

68

(41÷105)

T-ROOM DES 3

Room temperature setting in third enable time

68

(41÷105)

T REDUCED

Required room temperature setting during night
reduction

50

(41÷105)

T-ABSENCE

Required room temperature setting during holidays

59

(41÷105)

T-LIMIT DAY

Set the temperature value during heating time

66

(23 ÷104)

T-LIMIT N

Set the temperature value during reduction time

50

(23 ÷ 104)

HEATSLOPE

Set the Heatslope according to the installation

1,20

(0 ÷ 3)

ADAPTION

Only active if an FBR analogue room device is
connected and an outdoor sensor

0

(0 ÷ 1)

OPTIM HEAT

Activates the function for automatically starting the unit

10

(0 ÷ 20)

ADAP ROOM-T

Room sensor adaptation

0

(-9 ÷ 9)

OPTIM HEAT

Heating optimisation

0

(00 ÷ 02)

MAX OPT-TIME

The start of heating is brought forward by no more than
this time

2

(00 ÷ 03)

ECONO OPTI

Automatic reduction of burner disabling to the end of
set heating time

0

(00 ÷ 02)

PC-ENABLE

Code number for enabling access to heating circuit
data from a PC (0000= access is blocked)

0000

(0000÷9999)

SOLAR / MF
RETURN

NOT USED

NOTE:

Some menus are visible only if the relevant sensor is wired.