37 conversion from natural gas to propane gas – AERCO Modulex EXT 321 - 1123 User Manual
Page 77

MODULEX EXT 321, 481, 641, 802, 962, 1123 BOILERS
Installation, Operation & Maintenance Manual
3.37 Conversion From Natural Gas To Propane Gas
To convert the unit to use propane gas, instead of natural gas, do the following:
Converting From Natural Gas to Propane Gas
1. Set nominal heat by adjusting the fan speed parameter FH (FAN MAX) from the E8
controller as shown in Table 3-7, and Modulex EXT Pressure and CO
2
Level
Calibration in Table 3-6, above. This parameter requires a password to change.
2. Adjust CO
2
(%) minimum and maximum levels according to the type of gas as shown
in table below. See section 3.33, Burner Calibration for more information.
Gas Type
CO
2
Level (%) Minimum CO
2
Level (%) Maximum
Natural Gas
8.5
10
Propane Gas
10
11
3.
After gas conversion to propane and calibration, the gas installer should complete and
apply this label, or equivalent, as close to the rating label as possible:
Figure 3-42: MODULEX EXT Label
OMM-0087_0E
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913
Page 77 of 148
GF-143
Phone: 800-526-0288
12/01/14