7.5 Visual Inspection Of The Flame
The burner must flame evenly over the entire surface when operating correctly. The flame must
burn with a clear, ORANGE, stable flame. Check the flame through the flame observation port
(Figure 7-2). The flame pattern should resemble the flame in the illustration below.
FLAME COLOR:
• YELLOW
= CO2 HIGH NOT SATISFACTORY
• BLUE
= CO2 LOW NOT SATISFACTORY
• ORANGE
= OK
SATISFACTORY
Figure 7-2: Boiler Flame Observation Port Location
7.6 Proper Reassembly and Resealing of the Vent-Air Intake System
After removing, inspecting, and possibly cleaning the flue pipes and air intake, replace the
piping correctly. Refer to AERCO Venting Application Guide (GF-136-V) for information
concerning Modulex venting requirements.