MODULEX EXT 321, 481, 641, 802, 962, 1123 BOILERS

Installation, Operation & Maintenance Manual

Reversing Cold/Hot Water Flow & Return Connections

3.8.3

Change of Water Flow and Return connections from RIGHT hand to LEFT hand requires
reversing connectors, moving the Flow and Return Temperture Sensors to other end, and
exchanging positions of the Boiler Sensor KF and Automatic Air Vent.

WARNING!

Ensure that the gaskets for ALL connections are reversed along
with the connectors themselves.

3.8.3.1 Reversing Cold/Hot Water Flow & Return Piping Connectors

Refer to Figure 3-11 and reverse the connectors and end caps on Supply, Flow, and Return
pipes. Ensure that all gaskets are also reversed.

Figure 3-11: Reversing Cold/Hot Water Flow and Return Connections and

Sensors from RIGHT HAND to LEFT HAND

Move

end caps (and

gaskets) to other

end of

Flow/Return

pipes.

Reverse positions

of Boiler Sensor

KF and Automatic

Air Vent. See

Figure 3-13.

NOTE

Torque all bolts to 8.85 ft-lbs (12 N/m)

Move supply

connectors

(and

gaskets) to

other end of
Flow/Return

pipes.

Move Flow and Return

Sensors to other end of

pipes. See Figure 3-12.

Page 34 of 148

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

OMM-0087_0E

12/01/14

Phone: 800-526-0288