Figure 2.10, Input/output (i/o) box location, Installation – AERCO KC1000 Water Heater July 2011 User Manual

Page 15

Advertising
background image

INSTALLATION

2-7

Wiring for these features can be accomplished

in the I/O Box behind the left side panel (Figures

2.10 and 2.11). The I/O Box is common to both

KC1000 water heaters and boilers. While some

of the inputs and outputs are common to both

water heaters and boilers, some are not

applicable to both. These are noted in the

following paragraphs.

GAS SHUT-OFF VALVE

I/O BOX

BLOWER

Figure 2.10

Input/Output (I/O) Box Location

CAUTION!

DO NOT make any connections to the I/O

Box terminals labeled “NOT USED”.

Attempting to do so may cause equipment

damage.

2.6.1 OUTDOOR AIR SENSOR IN

Not applicable to Water Heaters.

2.6.2 AUX SENSOR IN

The AUX SENSOR IN terminals can be used to

add an additional temperature sensor for moni-

toring purposes. This input is always enabled

and is a view only input that can be seen in the

operating menu. The sensor must be wired to

the AUX SENSOR IN and SENSOR COMMON

and must be similar to AERCO BALCO wire

sensor P/N 12449. A resistance chart for this

sensor is located in APPENDIX C.

2.6.3 ANALOG IN

The ANALOG IN + and – terminals are used

when an external signal is used to change the

setpoint (Remote Setpoint Mode) of the heater.

Either a 4 to 20 mA /1 to 5 VDC or a 0 to 20 mA/

0 to 5 VDC signal may be used to vary the set-

point or air/fuel valve position. The factory

default setting is for 4 to 20 mA / 1 to 5 VDC,

however this may be changed to 0 to 20 mA / 0

to 5 VDC using the Configuration Menu

described in Section 3.

If voltage rather than current is selected as the

drive signal, a DIP switch must be set on the

PMC Board located inside the Control Box.

Contact the AERCO factory for information on

setting DIP switches.

All supplied signals must be floating (unground-

ed) signals. Connections between the source

and the Heater’s I/O Box must be made using

twisted shielded pair of 18–22 AWG wire such

as Belden 9841(see Figure 2.11). Polarity must

be maintained and the shield must be connected

only at the source end and must be left floating

(not connected) at the Heater’s I/O Box.

Whether using voltage or current for the drive

signal, they are linearly mapped to a 40°F to

240°F setpoint or a 0% to 100% air/fuel valve

position. No scaling for these signals is provided

2.6.4 B.M.S. (PWM) IN

Not applicable to Water Heaters.

2.6.5 SHIELD

The SHIELD terminals are used to terminate any

shields used on sensor wires connected to the

unit. Shields must only be connected to these

terminals.

2.6.6 mA OUT

These terminals provide a 4 to 20 mA output

that can be used to monitor setpoint ( 40°F to

240°F), outlet temperature (30°F to 240°F), or

air/fuel valve position (0% to 100% open). This

function is enabled in the Configuration Menu

(Section 3, Table 3.4).

2.6.7 RS-485 COMM

These terminals are used for RS-485 serial

communication between the unit and an external

“Master” such as an Energy Management

System or other suitable device.

2.6.8 EXHAUST SWITCH IN

These terminals permit an external exhaust

switch to be connected to the exhaust manifold

of the heater. The exhaust sensor should be a

normally open type switch (such as AERCO P/N

123463) that closes (trips) at 500

o

F.

2.6.9 INTERLOCKS

The unit offers two interlock circuits for inter-

facing with Energy Management Systems and

auxiliary equipment such as pumps or louvers or

other accessories. These interlocks are called

the Remote Interlock and Delayed Interlock

(Figure 2.11). The wiring terminals for these

interlocks are located inside the I/O Box on the

left side of the unit. The I/O Box cover contains a

wiring diagram which shows the terminal strip

Advertising