Troubleshooting – AERCO KC1000 Water Heater July 2011 User Manual

Page 66

Advertising
background image

TROUBLESHOOTING

7-2

KC1000 WATER HEATER TROUBLESHOOTING TABLE

FAULT INDICATION

PROBABLE CAUSES

CORRECTIVE ACTION

AIRFLOW FAULT

DURING IGNITION

1. Blower stopped

running due to

thermal or current

overload

2. Blocked Blower

inlet or inlet

ductwork

3. Blocked airflow

switch

4. Defective airflow

switch

1. Check combustion blower for signs of excessive heat or

high current drain that may trip thermal or current

overload devices.

2. Inspect the inlet to the combustion blower including any

duct work leading up to the combustion blower for signs

of blockage.

3. Remove the airflow switch and inspect for signs of

blockage, clean or replace as necessary.

4. Measure the airflow switch for continuity with the

combustion blower running. If there is an erratic

resistance reading or the resistance reading is greater

than zero ohms, replace switch.

AIRFLOW FAULT

DURING PURGE

1. Blower not running

2. Defective Air Flow

Switch

3. Blocked Air flow

Switch

4. Blocked Blower inlet

or inlet ductwork.

5. No voltage to switch

from control box.

1. Start the unit. If the blower does not run check the blower

solid state relay for input and output voltage. If the relay is

okay, check the blower.

2. Start the unit. If the blower runs, check the airflow switch

for continuity. Replace the switch if there is no continuity.

3. Remove the air flow switch and inspect for signs of

blockage, clean or replace as necessary.

4. Inspect the inlet to the combustion blower including any

ductwork leading up to the combustion blower for signs of

blockage.

5. Measure for 24 VAC during start sequence from each side

of the switch to ground. If 24VAC is not present refer to

qualified service personnel.

AIRFLOW FAULT

DURING RUN

1. Blower stopped

running due to

thermal or current

overload

2. Blocked Blower inlet

or inlet ductwork

3. Blocked airflow

switch

4. Defective airflow

switch

5. Combustion

oscillations

1. Check combustion blower for signs of excessive heat or

high current draw that may trip thermal or current overload

devices.

2. Inspect the inlet to the combustion blower including any

ductwork leading up to the combustion blower for signs of

blockage.

3. Remove the airflow switch and inspect for signs of

blockage, clean or replace as necessary.

4. Measure the airflow switch for continuity with the

combustion blower running. If there is an erratic

resistance reading or the resistance reading is greater

than zero ohms, replace the switch.

5. Run unit to full fire. If the unit rumbles or runs rough,

perform combustion calibration.

Advertising