INSTALLATION

2-10

In addition, Cold Air Damper # 99026 must be

installed. It should be located along the inlet duct

run as close as possible to the KC1000 (See

Figure 2.12). The Cold Air Damper must be

placed on individual sections (one Damper per

unit), not in a manifold section. The adjustment

screw on the Damper should be moved to the

center of the slot position and tightened 1/2 turn

past “finger-tight”. DO NOT over-tighten.

See AERCO Venting Guide GF-1050 for further

details.

6" MINIMUM

6x3 REDUCER

COLD AIR DAMPER

(FOR KC1000 LOW NOX)

Figure 2.12

Sealed Combustion Air Connection