Maintenance – AERCO KC1000 Water Heater July 2011 User Manual

Page 57

Advertising
background image

MAINTENANCE

6-13

5/8-11 HEX NUT

5/8-11 X 3" CAP SCREW

KC1000 SS HEATER

5/8 EYE NUT

5/8-11 X 4-1/2" STUD

UPPER HEAD

(P.N. 18842)

UPPER HEAD LINER

RELEASE GASKET

(P.N. 18556)

SHELL GASKET

(P.N. 18532)
SHELL RING


Cleaning the Heat Exchanger
Precautions:

Please review MSDS, specifications, and our website

www.aerco.com

for additional information, or call

technical service at (800) 526-0288.

N

OTICE

Mix the HydroSkrub with an equal volume of water to obtain a 50% concentration (11.5 gallons of each =

23 gallons total).

N

OTICE

If the isolation valves are located more than one foot from the supply and return ports of the exchanger,

add in the piping volume from the exchanger to the valves.

CAUTION!

Do not drain the unit without venting the shell! A vacuum in the unit may

displace the liner causing serious damage not covered by warranty.

Figure 6.17b

Carbon Water Heater Head

Configuration

Figure 6.17a

SS Water Heater Head

Configuration

5/8-11 x 4-1/2” STUD

MOUNTED IN THREADED

HOLE

Do not

remove

if using

a chain

hoist

Do not

remove

if using

a chain

hoist

5/8-11 x 3” BOLT

MOUNTED IN

THRU-HOLE

Advertising