Air shutter locking nut location, 4 propane combustion calibration, Initial start-up – AERCO KC1000 Water Heater July 2011 User Manual

Page 33

Advertising
background image

INITIAL START-UP

4-5

BLOWER

OUTLET

BLOWER

INLET

SCREEN

SHUTTER

SHUTTER

LOCKING NUTS

Figure 4.4

Air Shutter Locking Nut Location

REMINDER:

At 30% valve position, adjust only the differential

pressure regulator. At 100% valve position,

adjust only the inlet air shutter.

25. If the measured oxygen reading is above the

oxygen range in Table 3 (or 3A), loosen the

two 7/16" locking nuts securing the inlet air

shutter. Close the air shutter 1/4” to 1/2” to

decrease the oxygen level and tighten the

two nuts.

26. Allow the analyzer to settle then compare

the new oxygen reading to Table 3 (or 3A).

27. Repeat the adjustment until the oxygen is

within the specified range. Also, ensure that

the CO and NOx readings do not exceed the

values shown. Firmly tighten the inlet air

shutter locking nuts when finished.

NOTE:

Adjust the inlet air shutter only at 100% valve

position. Do Not adjust the differential pressure

regulator.

28. Change the valve position to 30%. Allow

time for the combustion analyzer to settle.

Check the measured oxygen level, CO and

NOx emissions to ensure that they are still

within the ranges shown in Table 1.

29. Continue these procedures until all oxygen

levels are within the ranges specified in

Tables 1, 2, 3 (or 3A).

30. Record all readings on the AERCO start-up

sheet provided with each unit. Proceed to

paragraph 4.5 when all natural gas

combustion calibration procedures are

completed.

IMPORTANT

The unit is shipped from the factory set up for

either natural gas or propane, as specified by

the Style No. on the Sales Order. If desired, the

unit can be easily switched from one fuel to the

other using the regulator spring change

procedure in Appendix I.

Since the required gas supply pressures for

propane differ from those required for natural

gas, the Propane Combustion Calibration

procedures are repeated in their entirety in

paragraph 4.4.

4.4 PROPANE COMBUSTION

CALIBRATION

The KC-1000 is shipped combustion calibrated

from the factory. Recalibration as part of a start-

up is necessary due to differences in altitude,

gas BTU content, gas supply piping and supply

regulators. Factory test data sheets are shipped

with each unit as a reference.

Prior to starting these procedures, ensure that

the KC1000 has been set up as specified in

paragraphs 4.2 through 4.2.4.

The following combustion calibration procedure

closely follows the factory procedure. By

following this procedure, readjustment of

combustion will be kept to a minimum.

1. Open the supply and return valves to the

unit and ensure that the system pumps are

running.

2. Open the gas supply valve(s) to the unit.

3. If a lockup style regulator is installed as a

gas supply regulator, adjust the gas supply

until a reading of 11” W.C. static pressure is

obtained.

4. Set the

ON/OFF switch to the OFF position.

Turn on AC power to the unit. The display

will show LOSS OF POWER and the time

and date.

Advertising