TROUBLESHOOTING

7-5

KC1000 WATER HEATER TROUBLESHOOTING TABLE – Continued

FAULT INDICATION

PROBABLE CAUSES

CORRECTIVE ACTION

(continued)

3. Defective High Gas Pressure Switch

3. Remove the leads from the high gas pressure switch and

measure continuity across the common and normally closed
terminals with the unit not firing. Replace the switch if it does not
show continuity.

HIGH WATER TEMP

SWITCH OPEN

1. Scaled BTU Transmitter.

2. Faulty Water Temperature Switch.

3. Faulty Temperature Sensor


4. Unit in MANUAL Mode

5. Unit setpoint is greater than Over

Temperature Switch setpoint

1. Inspect and clean the BTU transmitter per Maintenance Section.

2. Test the temperature switch to insure it trips at its actual water

temperature setting.

3. Using the resistance charts in Appendix C, measure the

resistance of Shell sensor and BTU sensor at a known water
temperature.

4. If unit is in Manual Mode, switch to Auto Mode.

5. Check setpoint of unit and setpoint of Temperature Switch.

Ensure that the temperature switch is set 20 degrees higher than
the unit’s setpoint.

HIGH WATER

TEMPERATURE

1. See HIGH WATER TEMP SWITCH

OPEN.

2. Temp HI Limit setting is too low.

1. See HIGH WATER TEMP SWITCH OPEN

2. Check Temp HI Limit Setting.

IGN BOARD

COMM FAULT

1. Communication fault has occurred

between the PMC board and
Ignition/Stepper (IGST) board

1. Press CLEAR button and restart unit. If fault persists, contact

qualified Service Personnel.