WATER HEATER DEFAULT SETTINGS - Continued

MENU & OPTION

FACTORY DEFAULT

Tuning Menu

Prop Band

8°F

Integral Gain

1.60

Derivative Time

0.10 min

Min Load Adj

0°F

Max Load Adj

0°F

FFWD Temp

N/A

Outlet Feedback

On

Feedback Gain

0.05

Breakpoint At 100%

77°F

Breakpoint At 90%

81°F

Breakpoint At 80%

85°F

Breakpoint At 70%

91°F

Breakpoint At 60%

95°F

Breakpoint At 50%

102°F

Breakpoint At 40%

110°F

Breakpoint At 30%

112°F

Breakpoint At 20%

114°F

Breakpoint At 10%

130°F

Breakpoint At 0%

135°F

Reset Defaults?

No