APPENDIX A

A-3

WATER HEATER MENU ITEM DESCRIPTIONS - Continued

MENU LEVEL & OPTION

DESCRIPTION

CONFIGURATION MENU
Internal Setpoint

Allows internal setpoint to be set. Default is 130°F.

Unit Type

Allows selection of Boiler or Water Heater.

Unit Size

Sets unit size from 0.5 to 3.0 MBTUs. Default is 1.0
MBTU.

Heater Mode

It allows selection of either the Constant Setpoint or
Remote Setpoint Mode. Default is Constant
Setpoint.

Remote Signal

Used to set the type of external signal which will be
used when operating in the Remote Setpoint Mode.
The factory default is 4-20 mA/1-5V.

Setpoint Lo Limit

Used to set the minimum allowable setpoint (40°F to
Setpoint Hi Limit). Default is 60°F

Setpoint Hi Limit

Used to set the maximum allowable setpoint
(Setpoint Lo Limit to 240°F). Default is 200°F.

Temp Hi Limit

This is the maximum allowable outlet temperature
(30 to 230°F). Any temperature above this setting
will turn off the unit. The temperature must then drop
5° below this setting to allow the unit to run. Default
Hi Limit is 215°F.

Max Fire Rate

Sets the maximum allowable fire rate for the unit
(40% to 100%). Default is 100%.

Aux Start On Dly

Specifies the amount of time to wait (0 to 120 sec.)
between activating the Aux Relay (due to a demand)
and checking the pre-purge string to start the boiler.
Default is 0 sec.

Failsafe Mode

Allows the Failsafe mode to be set to either Constant
Setpoint or Shutdown. Default is Shutdown.

mA Output

Can be set to allow this output to monitor Setpoint,
Outlet Temperature, Fire Rate Out, or be set to OFF.
Default is OFF.

Lo Fire Timer

Specifies how long (2 to 120 sec.) to remain in the
low fire position after ignition, before going to the
desired output. Default is 2 sec.

Setpt Limiting

Allows Setpt Limiting to be enabled or disabled.
Default is disabled.

Setpt Limit Band

When Setpt Limiting is enabled, this menu item
allows the Setpt Limit Band to be set from 0°F to
10°F. Default is 5°F.