HE-

111 − PIPING CONNECTIONS

Rev B Mar 2013

C-3

T

STEAM TO WATER HEAT EXCHANGER

SWDW (DOUBLE WALL DESIGN)

MULTIPLE UNIT INSTALLATION

NORTHVALE, NJ 07647

INTERNATIONAL, INC.

APPD.

DWN.BY

SCALE

DATE

MPC

122298

DATE

SCD

NTS

112498

AERCO

SD-A-369

F

REV.

BEYOND THE OUTSIDE DIAMETER OF THE HEAD TO PERMIT REMOVAL OF THE HEAD AND SHELL.

FITTINGS, ON THE WATER INLET SIDE, SHOULD BE LOCATED AS FAR AS POSSIBLE FROM THE HEATER.

4) REDUCERS, ON THE WATER INLET SIDE, SHOULD BE LOCATED ADJACENT TO THE HEATER. EXPANSION

5) CONDENSATE RETURN PIPING SHOULD BE ARRANGED TO PERMIT THE CONDENSATE TO DRAIN FREELY ,

6) DRAIN VALVE SHOULD BE PIPED DIRECTLY TO A FLOOR DRAIN. RELIEF VALVE & OVER-TEMP SOLENOID

2) PIPING TO THE UPPER HEATER HEAD SHOULD BE PROVIDED WITH UNIONS OR FLANGES WHICH ARE LOCATED

BY GRAVITY, FROM THE LOWER HEATER HEAD.

VALVE SHOULD BE PIPED VERTICALLY TO A HEIGHT 19" ABOVE THE FLOOR.

SEE DIMENSIONAL DRAWING.

NOTES:

3) HEATERS SHOULD BE PIPED REVERSE RETURN OR BALANCING DEVICES ON THE OUTLETS SHOULD BE

EMPLOYED.

1) FOR ACTUAL SIZES AND LOCATIONS OF PIPING AND OTHER CONNECTIONS TO THE HEATER,

HOT W

ATER

OUT

STEA

M HE

ADER

(NOT

E 5)

COLD

WAT

ER IN

HOU

SE R

ECIR

CULA

TION

(WHE

N EM

PLOY

ED)

CONNECTION

HOSE

CONNECTION

HOSE

CONNECTION

HOSE

P

T

T

C

C /

C /

CON

DEN

SATE

OUT

CHECK VALVE

STOP VALVE

PRESSURE GAUGE

PRESSURE GAUGE

THERMAL ELEMENT

DRAIN VALVE

RELIEF VALVE

CONTROL VALVE

P

C

COMPOUND

/

UNION

T

STRAINER

STEAM TRAP

TEMPERATURE GAUGE

LEGEND

/

Figure C-2. Piping Connection for Parallel Heat Exchanger