A.2 modbus communication information, He- 111 − appendix a – AERCO SWDW68 U-Tube Double-Wall Heaters w/ECS User Manual
Page 93
HE-
111 − APPENDIX A
Rev B Mar 2013
A-7
A.2 MODBUS COMMUNICATION INFORMATION
NOTE
The Eurotherm 2400 Controller supports the MODBUS RTU mode of
transmission. The default settings are as follows: 9600 Baud Rate, one
start bit, eight data bits, one stop bit and no parity bit.
Table A-1. Eurotherm Series 2400 Controller MODBUS Points
MODBUS
Data
Address
Menu
Item
Menu Item
Description
Units &
Range
Default/Comments
Register
Type
Ref. 1
Comm.
Guide
5
w.SP
Setpoint
40-205°F
140°F, Address to read value
Read
Only
5-4
24
SP 1
Setpoint
40-180°F
140°F, Address to change value
Write
5-11
1
Top
Value
Outlet Temp
40-205°F
Same value as front display
Read
Only
5-3
133
LoGH
Peak Temp
40-205°F
Resets on Power Loss
Read
Only
5-15
135
LoGA
Average
Temp
40-205°F
Resets on Power Loss
Read
Only
5-15
134
LoGL
Low Temp
40-205°F
Resets on Power Loss
Read
Only
5-15
13 (set)
74 (status,
0 = safe
1 = alarm)
AL 1
Over Temp
Alarm
40-205°F
20°F above setpoint; Alarm Type
17: Deviation High
Read
Only
5-7
5-20
14 (set)
74 (status,
0 = safe
1= alarm)
AL 2
(FSH)
Full Scale
High Alarm
205°F
205 ° F
Alarm Type 2: Full Scale High
Read
Only
5-7
5-20
258
Sbr
Feedback
Sensor
Break
Status:
0: Good
1: Failed
Denotes Feedback Sensor
Failure/Open Circuit
Read
Only
5-18
289
Li 1
Feedback
Sensor Temp
40-180°F
Sensor input to controller, same
as display temp.
Read
Only
5-14
290
Li 2
Flow
GPM
Read
Only
5-14
3
OP
Control
Output
Signal
%
Correlates to valve position
Read
Only
5-4
131
Addr
Communicati
on Address
Integer
(0-63)
Default – 1. Temperature
Controller communication
address
Read
Only
5-14
REFERENCE DOCUMENTS
1. Eurotherm 2000 Series Communications Handbook, # HA026230
2. Eurotherm 2404/2408 Control Setpoint Programmer Installation and Operation Handbook,
# HA025132