American Access Systems Touch Plate Reader - 11-65000 User Manual

Page 12

Advertising
background image

Page 12 American Access Systems / Security Brands, Inc.

Card Status

Reports on the status of Access Cards may be obtained by choosing 2 (Cards) from the Main Menu and then
selecting 3 (Display Card Status) from the Cards Menu. Card status is always displayed in numerical order of the block
specified. If a particular Time Zone is selected, only those cards of the selected block that are in the Time Zone will be
displayed. If “ALL” is chosen for the Card Time Zone entry, all cards of the selected block will be displayed.
If a particular Time Zone is chosen, the number of the card, the limited use status (i.e., None, Days, Weeks, Uses, or
Times), and the remaining uses, days, weeks, or the times access has been granted will be displayed. If “ALL” is
selected, the same information as above plus the Time Zone of each card will be displayed.

Antipassback Forgive

This selection allows you to specify all cards or a range of cards to be immediately set to a Neutral status for Real
Antipassback. This allows access to any card previously denied access due to a Real Antipassback violation (e.g.
attempting a second badging at an IN reader). This only affects cards programmed into Time Zones with Real
Antipassback enabled. The range may be set to apply to one card or all cards. Once forgiven, a card’s Real
Antipassback status (IN or OUT) will be determined by the next Real Antipassback reader in which the card is used.
For more information on Antipassback, see page 24.

Frogive Antipassback using the Menu System

Choose 2 (Cards) from the Main Menu, then choose 4 (Antipassback Forgive) from the Cards Menu. You may then
specify All or Range. If you select Range, you must enter beginning and ending card numbers for the range and
enter Y (Yes) to the confirmation prompt.
FORGIVE ANTIPASSBACK USING THE PROGRAMMING DECK To forgive antipassback for all cards using the
programming deck, place the * card on the TOUCH CARD® reader plate followed by the SET TIMER card. You cannot
forgive a range of cards using the program deck.

Antipassback Disable/Enable

Occasionally, due to a gate or door at an IN or OUT reader being temporarily inoperative, cardholders’ antipassback
status may become out of sync, necessitating the disabling of antipassback at the reader. Although this can
be done with the SA-NET TM software by disabling APB in all applicable Time Zones, it may be simpler to make a
temporary change using the program deck.
To disable antipassback at a reader using the program deck, place the VOID card on the TOUCH CARD® reader
plate followed by the SET TIMER card. This will allow access to any otherwise valid card regardless of that card’s
current IN/OUT Antipassback status.
To re-enable antipassback at a reader using the program deck, place the VALID card on the TOUCH CARD® reader
plate followed by the SET TIMER card.