System purging, Initial start-up – AXEON R2-Series User Manual

Page 18

Advertising
background image

18

R2-Series User’s Manual

11/13/12

MKTF - 212

SYSTEM PURGING

Carefully inspect your system before initial start-up. Check that all plumbing and electrical connections
are not loose or have not come undone during shipment. A User’s Manual, Test Results, and Filter
Housing Wrench will accompany your R2-Series Reverse Osmosis System.

NOTE: LEAVE THE POWER TO THE SYSTEM OFF FOR THIS PROCEDURE.

1.

Redirect permeate water to the drain for this procedure.

2.

Fully open the concentrate valve (Counter Clockwise). (Figure 1B, Page. 15)

3.

Fully open the throttle valve (Counter Clockwise). (Figure 1B, Page. 15)

4.

Press and hold the reset button on the controller for three seconds to activave the solenoid

bypass feature.

INITIAL START-UP

1.

Maintain the permeate water line to drain for this

procedure.

2.

Fully open the concentrate valve (Counter Clockwise).

(Figure 1B, Page. 15)

3.

Adjust the throttle valve at 50% open (Figure 1B,

Page. 15)

4.

Turn the RO system on and adjust the concentrate

(waste) valve and the throttle valve to the specified

system’s production, recovery and operating pressure.

(Figure 1B, Page. 15)

5.

Inspect the system for leaks.

6.

Allow the system to run 30 minutes to flush the

preservative solution from the system.

7.

After 30 minutes, shut down the system.

8.

Re-direct the permeate water back to the tank or point-of-use.

9.

Record the readings daily for a week; after one week record the readings regularly.