Features

■ Field Selectable from 2 to

10 Outputs

■ Completely Solid-state

Timing and Switching
Logic

■ 300% Overrated Solid-

state Switch

■ Pressure Switch Control

Option On Board

■ 12 to 24 Volts D.C. Input

Voltage

■ Adjustable "On" and "Off"

Times

■ High Quality Locking

Bushing Potentiometers
for Timing Adjustment

■ Very Low Power

Consumption

■ RTV Protective Coating

for Corrosion and
Moisture Resistance

■ LEDs Show

Compartment Being
Cleaned

■ Metal Chassis Provided

For Mounting Directly
Into NEMA-4 Enclosure

Operating Logic: The control can function in 2
modes:

Continuous Mode: The pressure switch terminals
are shorted. Upon application of output voltage,
the control activates output #1 after the preset off
time. It will continue to activate outputs sequen-
tially until input voltage is removed.

On Demand Mode: The pressure switch termi-
nals are connected to an isolated set of contacts of
a differential pressure switch. The control will acti-
vate the outputs sequentially whenever the pres-
sure switch contacts are closed. When the pressure
switch contacts open, the output sequencing stops.
Re-closing of the contacts will cause the control to
resume activating the outputs.

Program wire allows the user to select the maxi-
mum number of outputs to be activated.

DC Input, Pulse
Cleaning of bag
House Dust
Collectors Model

DNC-T2010-ADC

Dust Collector
Controls

No. of

Outputs

2 - 10

12 - 24 VDC

1.5 - 60

DNC-T2010-ADC

Input Voltage

Off Time

(In Seconds)

Part Number

Time Setting Ranges

On Time: Adjustable from 20 to 200 millisec-

onds

Off Time: Adjustable from 1.5 to 60 seconds
Repeatability: ±3% over temperature & voltage

ranges

Input

Operating Voltage: 10.0 to 29.0 VDC

(Unfiltered supply voltage must be full-wave
rectified.)

Power Consumption Voltage During Off

Time: 1.5 Watts @ 12 VDC, 4.2 Watts @ 24
VDC

Output

Type: Solid-state switch
Load Per Output: 3 Amp maximum @ 1.5 V

less than input voltage

Protection

Transient Input Voltage: Metal oxide varistor

plus large filter capacity

Transient Output Voltage: Solid-state switch

rated at 10 Amps. - 60 Volts fly-back diode pro-
tected

Short Circuit Protection: 3 Amp fuse for circuit,

Reverse polarity protected

Environmental

Operating Temperature: -40°F to 150°F

(-40°C to 60°C)

Storage Temperature: -40°F to 185°F

(-40°C to 85°C)

Specifications