Pulsing failure of all valves or the same numbered valve on each

header

Pulse timer board inoperative

Check pulse timer board for 120 VAC pulse between each numbered

terminal on timer board and solenoid common terminal. Repair or

replace timer if necessary.

Open or short circuit in wiring between pulse timer board and

solenoids

Check continuity with ohmmeter or suitable tester and repair as required.

Pulsing failure of valves at any location

Plastic plug in solenoid exhaust port

Remove and discard plug.

Ruptured diaphragm

Disassemble valve in question and inspect diaphragm(s). Replace with a

repair kit if necessary.

Pinched or plugged tubing between solenoid and diaphragm valve.

Inspect tubing and replace if necessary

.

Continuous passage of compressed air through one of more

blowpipes

¼” O.D. tubing or fittings disconnected, leaking or broken.

Inspect and repair as required. Always use new ferrules in fittings when

replacing copper tubing.

Diaphragm valve air bleed hole or passage restricted

Disassemble and inspect the diaphragm valve in question as follows:

1” valves – check for plugged air bleed passages in valve body and cover.

1 ½” valves – check for plugged or restricted air bleed passages.

2” valves – check for plugged or restricted air bleed passages.