2-23

Cisco XR 12416 and Cisco XR 12816 Router Chassis Installation Guide

OL-17440-01

Chapter 2 Preparing for Installation

Site Requirement Guidelines

To ensure a satisfactory supplemental ground connection to the router, use the
following parts:

Note

These parts are not available from Cisco, but are available from commercial
vendors.

Two grounding lugs, which have two M6 bolt holes with 0.625 to 0.75-inch
(15.86 to 19.05-mm) spacing between them, and a wire receptacle large
enough to accept a 6-AWG or larger, multistrand copper wire. This lug is
similar to those used for the DC-input power supply leads (see

Figure 2-7

).

Two M6 hex-head nuts and locking washers (nickel-plated brass is ideal).

Two grounding wires. Although we recommend at least 6-AWG multistrand
copper wire, the wire diameter and length depend on your router location and
site environment.

Site Wiring Guidelines

When planning the location of the router, consider distance limitations for
signaling, electromagnetic interference (EMI), and connector compatibility. If the
wiring is run for any significant distance in an electromagnetic field, interference
can occur between the field and the signals on the wires. Poor wiring can cause:

Radio interference emanating from the wires.

Strong EMI, especially when caused by lightning or radio transmitters. EMI
can destroy the signal drivers and receivers in the router, and can even create
an electrical hazard by conducting power surges through lines and into
equipment.

Note

To predict and remedy strong EMI, you may need to consult with experts
in radio frequency interference (RFI).