2-17

Cisco XR 12416 and Cisco XR 12816 Router Chassis Installation Guide

OL-17440-01

Chapter 2 Preparing for Installation

Site Requirement Guidelines

AC-Powered Routers

AC PEMs operate in the nominal range of 200 VAC to 240 VAC and require a
minimum service of:

20 A for operation in North America

16 A for international operation

13 A for operation in the UK

Each of the AC power inputs requires separate dedicated branch circuit. For a list
of the nominal and acceptable value ranges for source AC power, refer to

Table A-2 on page A-3

.

Figure 2-6

shows different styles of AC power cords used to connect to the local

AC power source that are available for North America and various locales.

Figure 2-6

AC Power Cord Plugs and Appliance Coupler

26044

North America

Rewirable twist-lock plug

NEMA L6-20P (20A)

Australia, New Zealand

SAA/3 plug

AS/NZZS 3112-1993 (15A)

Europe, Argentine, Brazil

VIIG plug

CEE (7) VII (16A)

Appliance coupler

C19W coupler

Hot EN60320/C19 (20A)

Italy

1/3/16 plug

CEI 23-16 (16A)

United Kingdom

BS89/13

BS 1363/A

(13A; replaceable fuse)