Weighing module upgrade – Flintec II IPC User Manual

Page 11

Advertising
background image

FlintWeigh II IPC Technical Manual, Rev. 1.06 November 2011

Page 11 of 36

4.4. Weighing Modules for the Operation of Standard Load Cells

The weighing system controller can accommodate up to two weighing modules. Depending on the application –
legal for trade scale or industrial application – it can be selected among various weighing modules.

Weighing module type

LDU 68.1

LDU 69.1

LDU 78.1

LDU 68.2

Accuracy class

Not approved

Certificate no.

DK0199-R76-

10.04 Rev.1

DK0199-R76-

11.08 Rev. 1

DK0199-R76-

10.08 Rev. 1

Intervals "n" acc. Kompmodeng:

n

ind

10.000

10.000

10.000

Internal resolution

± 130 000

> ± 1 000 000

± 260 000

± 130 000

Approved single range scale

yes

yes

yes*

no

Approved multi range scale

no

yes

yes*

no

Approved multi interval scale

no

yes

yes*

no

Load cell excitation

U

EXC

5 V DC

5 V AC

5 V DC

5 V DC

Minimum input voltage

U

MIN

0 V

0 V

0 V

0 V

Approved min. input per vsi

U

min

1.0

µ

V

0.1

µ

V

0.3

µ

V

Input sensitivity

0.05

µ

V/d

0.02

µ

V/d

0.05

µ

V/d

0.1

µ

V/d

Min. load cell impedance

R

Lmin

87.5

87

87.5

87.5

Max. load cell impedance

R

Lmax

1150

1200

1150

1150

Min. operation temperature

T

min

-15 °C

-15 °C

-15 °C

-15 °C

Max. operation temperature

T

max

+55 °C

+55 °C

+55°C

+55 °C

Fractional error limit

P

ind

0.5

0.5

0.5

Load cell connection

4-/6- wire technique

4/6

4/6

4/6

4/6

Factory sensor addresse (RS485-ID)

1 (2)

3 (4)

5 (6)

7 (8)


Tab. 4.3: Technical characteristics of weighing modules

Hint: If two weighing modules of the same type are used, then the sensor address of the second module is
increased by one (see RS485-ID in parentheses).

4.5. Weighing Module Upgrade

You can upgrade the weighing system controller with a second weighing module. Auch eine Umrüstung der
Wägemodule ist möglich.

ATTENTION: LEGAL FOR TRADE APPLICATIONS

If any of the relevant weighing components will be changed, the operating license als legal for trade scale
expires. Please read chapter 9 to this.

IMPORTANT:

For all service operations use an appropriate protection against electrostatic
discharge. Follow the safety instructions within the operation manual of your
instrument.

Step 1:

Shut down your operating system. Disconnect the weighing terminal from the power
source. Open the enclosure of the weighing terminal.

Step 2:

Remove the interlock of the PCI plug-in card. Afterwards you can take out the
weighing system controller.

Step 3:
(only for retrofit)

Remove the wire strap from the weighing module to replace and remove the two M3
x 6 mm cross slot screws. Pull out the weighing module.

Step 4:

Insert the new weighing module into the corresponding socket. Secure the weighing
module by fastening the supplied M3 x 6mm cross slot screws.