2 adjustment at plc, 3 testing the scale performance – Flintec FAA-26 User Manual

Page 12

Advertising
background image

FAA-26, Technical Manual, Rev. 1.1, June 2014

Page 11 / 13

The analog output value at any loading is

Analog

Output

= Minimum output +

Maximum output

– Minimum output

* Load

Scale capacity


Example:
Scale capacity

100kg

Output range

4

– 20 mA

Load

25kg


The 4-20mA analog output current will be ;

I

out

= 4mA + (( 20mA

– 4mA ) / 100kg ) * 25kg = 4 + 0.16 * 25 =

I

out

= 8 mA

The 0

– 10 VDC analog output voltage will be:


V

out

= 0 + (10V / 100kg ) * 25 kg = 0,1 * 25 =

V

out

= 2.5 VDC

Increase or decrease the analog output by gain adjustment rotary switch to measure
the calculated output value above. Please make gain adjustment rotary switch

0

position.

5.2 Adjustment at PLC

All instruments are adjusted in the production to operate in its analog output range
between 0 mV and 10 mV load cell signal as default (only for 2mV/V load cells).
Current output default adjustment is 4

– 20 mA and Voltage output default range is

0

– 10 VDC .


For example if the instrument is at factory default values and programmed to operate
4

– 20 mA output range, the output will be 4 mA at 0 mV load cell signal and will be

20 mA at 10 mV load cell signal.

Changing the FAA-26 instrument the re-calibration is not required because of
matching instruments in production at Flintec.

5.3 Testing the Scale Performance

You should check your scale performance by testing the scale eccentricity, scale
linearity at loading up to maximum loading value, repeatability etc. before using it

.