4. Use 1/2” threaded rod to hang the AC-PSP. Install the threaded rod and angle that will be used

to hang the assembly from the ceiling joists. Drill 9/16” holes as needed in the angle for the
threaded rod. Be sure to line up with the welded-on angle mounting brackets on the AC-PSP.

5. Peel the protective plastic coating on the hood down below where the bottom edge of the AC-

PSP will rest against the hood so it does not remain behind the AC-PSP.

6. Move the AC-PSP into position as indicated by the project submittal drawings; lining up the top

edge of the AC-PSP with the top edge of the hood. Remove the protective plastic coating from
the back of the AC-PSP. See Figure 13a and 13b.

7. Install the threaded rod into the AC-PSP hanging angles and use heavy-duty nuts to secure the

connection. Adjust tension on hanging rods to position AC-PSP so it fits flush with the hood.

8. Caulk the seams between the hood(s) and the AC-PSP assembly, as well as between adjacent

AC-PSP assemblies (if applicable) after the hood(s) and hood accessories have been installed.

AC-PSP Installation

Figure 13A

AC-PSP Installation

Figure 13B