Configuration and diagnostics, Security, Setup options – FloAire Demand Control Ventilation System User Manual
Page 19

A0023662
May 2014 Rev.5
19
Configuration and Diagnostics
Security
1. To access the Configuration / Factory, the password 1111 must be used.
2. To access the Configuration / Fire Options, the password 1234 must be used.
Setup Options
The ECPM03 board allows the user to monitor the system and configure a broad range of options
associated with the functionality of the system. Monitoring is done through the setup menus on the
ECPM03 LCD as shown above. Configuration is done through the HMI after calling for Configuration
through the ECPM03 menu.
Below the ECPM03 LCD are 4 buttons for navigation: MENU, UP, DOWN, ENTER. When in configuration
mode, the four buttons on the HMI will be labeled the same. See picture above.
The MENU button typically takes you up one level in the menu tree while the ENTER button takes you
down one level. UP and DOWN navigate through the same level of the menu tree and also allow the user
to change the value of a parameter.
After changing some parameters in the configuration menus, the user needs to press MENU multiple
times on the HMI
until the screen displays the message “Saving. Wait for reboot” As indicated, the
processor will reboot. This allows the board to correctly process the parameters changed.
NOTE: a reboot of the board will cause the electric gas valve (if equipped) to shut off. Confirm that
gas/pilot lights are re-lit if necessary. It will also cause the VFDs to stop if not in Auto mode.
The 4 items below can be accessed through the ECPM03 LCD:
a. Display System Information
Starting from the Main menu, press the DOWN button, press DOWN again. Screen displays
“Info”.
Press the ENTER button. Screen displays
“Fault History”. Press DOWN to View the Version number.
Press DOWN to view the package Type, which should be
“DCV”.
b. Display Fault History
Starting from the Main menu, press the DOWN button, press DOWN again. Screen displays
“Info”.
Press the ENTER button. Screen displays
“Fault History”. Press ENTER. Press UP and DOWN to
scroll through the fault history, with 1 being the most recent fault. To clear the fault history, please
ENTER and press ENTER again when prompted “Clear Fault History”. Or press MENU to go back
without clearing.