FloAire Demand Control Ventilation System User Manual

Page 5

Advertising
background image

A0023662

May 2014 Rev.5

5

FIELD WIRING: The following is for reference only. All 120 Volt AC field wiring is landed on terminal
blocks, not on the board itself. See Installation section for details. Low voltage class 2 field wiring may be
landed at J3, J4, J5, or J10 connectors only, as indicated by the panel labeling and installation schematic.
Provision for spacing and routing of the field wiring is provided in the panel.

FACTORY WIRING:
The connectors below are intended to be used for factory wiring only by a UL508A panel shop:
J7, J8, J9 are provided for the control of 120 Volt AC relays, contactors, solenoids and shunt trip
breakers. Under no circumstances shall any lighting or motor loads be directly connected to these
connectors.

J1, J2, J6, are reserved for low voltage class 2 factory wiring.

Control Board (ECPM03) diagram

Advertising