AV: 12: Heating Valve Output. This is the output, in percentage, of the PID loop which feeds the

heating valve. A value of 0% is low fire, and a value of 100% is high fire.

Properties

- Fixed readout. Non-editable. This value is determined by comparison of

AV: 4 to AV: 9 using the PID loop

- BACnet Reference: htg_vlv_out

- Modbus Register: 40023

- N2 Register: 12

- Lonworks ID: nvoHeatVlvOut

- Units of percentage

- Range: 0.0 to 100.0%


AV: 13: VFD Speed Input. This is the network input, in volts (V), of which will be used by the

controller to send out a 0 to 10 V signal to an internal VFD. For externally network controlled

VFDs, this AV is not to be used.

Properties

- Editable, precision to the tenth decimal place

- BACnet Reference: vfd_spd_in

- Modbus Register: 40041

- N2 Register: 21

- Lonworks ID: nviVFDSpdInput

- Units of Volts

- Range: 0.0 to 10.0


AV: 14: VFD Speed Output. This is the output, in volts (V), which is being sent to the VFD by the

controller. This is for internally controlled VFDs only. This AV is simply a confirmation of

receiving the input from AV:13.

Properties

- Fixed readout. Non-editable.

- BACnet Reference: vfd_spd_out

- Modbus Register: 40043

- N2 Register: 22

- Lonworks ID: nvoVFDSpdOut

- Units of Volts

- Range: 0.0 to 10.0


AV: 15: Modulating Damper Input. This is the network input, in volts (V), of which will be used by

the controller to send out a 0.0 to 10.0 V signal to the modulating damper.

Properties

- Editable, precision to the tenth decimal place

- BACnet Reference: mod_dmp_in

- Modbus Register: 40029

- N2 Register: 15

- Lonworks ID: nviModDmpInput

- Units of Volts

- Range: 0.0 to 10.0