FloAire DDC User Manual

Page 9

Advertising
background image

9

AV: 8: Cooling Stage 2 Offset. This is the offset value from AV:6, which will activate the second

stage cooling. If the Intake Air Temperature rises above AV:6 + AV:8, 2

nd

stage cooling will

enable.

Properties

- Editable, precision to the tenth of a degree

- BACnet Reference: cl_s2_ofst

- Modbus Register: 40009

- N2 Register: 5

- Lonworks ID: nviCoolTwoOfst

- Units of degrees Fahrenheit (can be changed in software)

- Range: 1.0 to 30.0


AV: 9: Effective Discharge Air Temperature. This is the effective discharge air temperature, as

read from the unit’s internal discharge air sensor.

Properties

- Fixed readout. Non-editable

- BACnet Reference: edat

- Modbus Register: 40015

- N2 Register: 8

- Lonworks ID: nvoEffDisAirTemp

- Units of degrees Fahrenheit (can be changed in software)

- Range: -25.0 to 225.0

- Type II 10K Thermistor


AV: 10: Cooling Stage 1 Off Delay. This is the time, in minutes, of which the stage 1 cooling

must remain on after stage 2 cooling has been disabled. This prevents cycling between stage 1

and stage 2 cooling.

Properties

- Editable using integer values only

- BACnet Reference: s1_cl_dly

- Modbus Register: 40007

- N2 Register: 4

- Lonworks ID: nviCoolOneOffDly

- Units of minutes

- Range: 1 to 30

- Default: 5


AV: 11: Cooling Stage 2 On Delay. This is the time, in minutes, of which the stage 1 cooling must

be on before stage 2 cooling is allowable. This prevents abrupt cooling demand if the network

were to have a large fluctuation of intake air temperature values.

Properties

- Editable using integer values only

- BACnet Reference: s2_cl_dly

- Modbus Register: 400011

- N2 Register: 6

- Lonworks ID: nviCoolTwoOnDly

- Units of minutes

- Range: 1 to 30

- Default: 5