AV: 20: Space (Room) Air Temperature Sensor. This variable provides the room air temperature
sensor reading from the field installed sensor.

Properties

- Fixed readout. Non-editable

- BACnet Reference: rat_sensor_visible

- Modbus Register: 40043

- N2 Register: 22

- Lonworks ID: nvoRoomTSensor

- Range of -25.0 to 225.0

- Units of degrees Fahrenheit (can be changed in software)

- Type II 10K Thermistor

AV: 21: Heating Room Temperature Setpoint. This variable is used to activate the space heating
function. This occurs when BV:17 is set to “On” or “Space” and the space temperature (AV:20)
falls below the space heating setpoint (AV:21 minus AV:22). Used as a space heating function.

Properties

- Editable, precision to the tenth of a degree.

- BACnet Reference: rt_heat_stpt

- Modbus Register: 40037

- N2 Register: 19

- Lonworks ID: nviRoomTStpt

- Units of degrees Fahrenheit (can be changed in software)

- Range: 50.0 to 90.0

- Default: 70.0

AV: 22: Heating Room Temperature Setpoint Differential. This variable is used to adjust the
space heating setpoint differential to keep space heating supply temp from bouncing.

Properties

- Editable, precision to the tenth of a degree.

- BACnet Reference: rt_heat_stpt_diff

- Modbus Register: 40039

- N2 Register: 20

- Lonworks ID: nviRoomTDiff

- Units of degrees Fahrenheit (can be changed in software)

- Range: 1.0 to 10.0

- Default: 2.0