FloAire DDC User Manual

Page 18

Advertising
background image

18

-

Network Reference: oad_rntm

-

Modbus Register: 10023

-

N2 Register: 23

-

Lonworks ID: nvoOadRntmAlm

-

Activates if BV: 7 has been in the On state for 10000 hours.


BV: 42 SAT_HI: High Supply Air Temperature.

-

Network Reference: sat_hi

-

Modbus Register: 10024

-

N2 Register: 24

-

Lonworks ID: nvoSATHiAlm

-

Activates if AV: 9, the Discharge Air Temperature, is greater than 160 Degrees for 10:00
minutes, and the unit has proper airflow.


BV: 43 SAT_LO: Low Supply Air Temperature.

-

Network Reference: sat_lo

-

Modbus Register: 10025

-

N2 Register: 25

-

Lonworks ID: nvoSATLoAlm

-

Activates if AV: 9, the Discharge Air Temperature, is less than 35 Degrees for 10:00 minutes,
and the unit has proper airflow.


BV: 44 SF_FAIL: Supply Fan Failure.

-

Network Reference: sf_fail

-

Modbus Register: 10026

-

N2 Register: 26

-

Lonworks ID: nvoSfFailAlm

-

Activates if BV: 3, the Supply Fan Command, is Off, however BV: 4, the Supply Fan Status, is
On. There is a 30 second feedback delay.


BV: 45 SF_HAND: Supply Fan In Hand.

-

Network Reference: sf_hand

-

Modbus Register: 10027

-

N2 Register: 27

-

Lonworks ID: nvoSFHandAlm

-

Activates if BV: 3, the Supply Fan Command, is On, however BV: 4, the Supply Fan Status, is
Off. There is a 30 second feedback delay.

BV: 46 SF_RNTM: Supply Fan Runtime Expired.

-

Network Reference: sf_rntm

-

Modbus Register: 10028

-

N2 Register: 28

-

Lonworks ID: nvoSfRntmAlm

-

Activates if BV: 4 has been in the On state for 10000 hours.

BV: 47 SMOKE: Smoke Detector Alarm.

-

Network Reference: smoke

-

Modbus Register: 10029

-

N2 Register: 29

-

Lonworks ID: nvoSmokeAlm

-

Activates if BV: 14, the Smoke Detector Status, is in the On state. There is no delay.

-

This alarm is a shutdown alarm.