BV: 11: 2nd Stage Cooling Command. This is the command used to activate the stage 2 cooling

output from the controller.

Properties

- Fixed readout. Status only.

- Network Reference: s2_clg_cmd

- Modbus Register: 10001

- N2 Register: 1

- Lonworks ID: nvoCoolTwoCmd

- Activates from either BV: 10 or when the call for second stage cooling logic is satisfied

using AV: 2, AV: 7, and AV: 8



BV: 12: Heat On Command. This is the command used to activate the call for heat relay.

Properties

- Fixed readout. Status only.

- Network Reference: ht_on_cmd

- Modbus Register: 10004

- N2 Register: 4

- Lonworks ID: nvoHeatOnCmd

- Activates when a call for heat is determined from comparison of AV: 2 to AV: 5


BV: 13: Clogged Filter Status. This is the status of the clogged filter input to the controller. A

value displayed here is only relevant if the clogged filter option was ordered with the unit.

Properties

- Fixed readout. Status only.

- Network Reference: fltr_sts

- Modbus Register: 10003

- N2 Register: 3

- Lonworks ID: nvoClogFltrSts

- Activates when the clogged filter input is On. An On state is the normal run condition.

An Off state indicates clogged filter. A clogged filter alarm will sound (see alarm section).


BV: 14: Smoke Detector Status. This is the status of the smoke detector input to the controller.

A value displayed here is only relevant if the smoke detector option was ordered with the unit.

Properties

- Fixed readout. Status only.

- Network Reference: smk_sts

- Modbus Register: 10009

- N2 Register: 9

- Lonworks ID: nvoSmokDtctSts

- Activates when the smoke detector input is On. An On state is the alarm state

condition. A Smoke alarm will sound and shut down the unit (see alarm section).


BV: 15: Emergency Alarm. This is the network input for an emergency alarm. If the network

value of this input is changed to On, the unit will shut down.

Properties

- On/Off Switch

- Network Reference: emerg_alm_in

- Modbus Register: 4

- N2 Register: 4

- Lonworks ID: nviEmerAlarmOn