Ix fuel line piping warning – Crown Boiler TWZ175 User Manual

Page 19

Advertising
background image

17

FIGurE 14: tanKlEss HEatEr PIPInG

IX Fuel line Piping

WARNING

• UNDER NO CIRCUMSTANCES CAN COPPER WITH SWEAT STYLE CONNECTORS

BE USED.

• DO NOT USE COMPRESSION FITTINGS.
• OIL PIPING MUST BE ABSOLUTELY AIRTIGHT OR LEAKS OR LOSS OF PRIME

MAY RESULT.

• SOME JURISDICTIONS REQUIRE THE USE OF A FUSIBLE SHUTOFF VALVE AT

THE TANK AND/OR THE BURNER. IN ADDITION, SOME JURISDICTIONS REQUIRE
THE USE OF A FUSIBLE ELECTRICAL INTERLOCK WITH THE BURNER CIRCUIT.
CHECK YOUR LOCAL CODES FOR SPECIAL REQUIREMENTS.

Fuel line piping design, materials and construction must be in accordance with local building codes, requirements of the lo-

cal authority having jurisdiction, and, the latest edition of the Standard for the Installation of Oil-Burning Equipment (ANSI/

NFPA 31) in the United States and CSA B139-04 for installation in Canada. Refer also to the instruction manuals provided

with the burner and oil pump.