Warning – Crown Boiler TWZ175 User Manual

Page 26

Advertising
background image

24

23) Check for clean cutoff of the burner. Air in the oil line between fuel pump and nozzle will compress, while burner is

running, and expand, when burner shuts off, causing oil line pressure to drop and nozzle drip after burner stops. Cycle burner

on and off 5 to 10 times to purge air completely.
24) Check thermostat operation by raising or lowering its set point as required, cycling burner on and off.
25) Verify primary control operation and safety features according to procedure outlined in the instructions furnished with

control.
26) Check high limit control operation. Jump thermostat terminals and allow burner to run until boiler water temperature

exceeds high limit setting. The burner should shut down, and circulator continue running. Allow the temperature to drop

below the control setting. The burner must restart. Boiler installation is not complete unless these checks are made and are

satisfactory. Remove thermostat jumper and reconnect thermostat upon check completion.
27) After the boiler has operated for approximately 30 minutes, check the boiler and heating system for leaks. Repair any

leaks found at once.
After the above checks have been completed, leave thermostat(s) at desired setting. Leave all instructions provided with the

boiler with owner or in boiler room, displayed near boiler.

taBlE 3a: BEcKEtt BurnEr cOnFIGuratIOn anD sEtuP Data

TWZ065 TWZ075 TWZ100 TWZ090 TWZ125 TWZ150 TWZ120 TWZ175 TWZ200

BURNER MODEL

AFG

AFG

AFG

AFG

AFG

AFG

AFG

AFG

AFG

AIR TUBE COMBO.

70MMAQ 70MMAQ 70MMAQ 70MMAQ 70MDAQ 70MDAQ 70MLAQ 70MLAQ 70MLAQ

HEAD TYPE

L1

L1

L1

L1

V1

V1

V1

V1

V1

3 3/8

3 3/8

3 3/8

3 3/8

2 3/4

2 3/4

NONE

NONE

NONE

INSERTION LENGTH

2 1/4

2 1/4

2 1/4

2 1/4

2 1/4

2 1/4

2 1/4

2 1/4

2 1/4

PITCH ANGLE

2

2

2

2

2

2

2

2

2

STANDARD

HAGO

HAGO

HAGO

DEL.

HAGO

HAGO

HAGO

HAGO

HAGO

NOZZLE

0.55/60B 0.65/60B 0.85/60B 0.75/60B 1.00/60B 1.25/60B 0.90/60B 1.35/45B 1.50/45B

ALTERNATE

DEL.

DEL.

DEL.

HAGO

DEL.

DEL.

DEL.

DEL.

DEL.

NOZZLE

0.55/60W 0.65/60W 0.85/60W 0.75/60B 1.00/60B 1.25/60B 0.90/60B 1.35/45B 1.50/45B

PUMP PRESS (psi)

140

140

140

140

140

140

175

175

175

HEAD SETTING

NA

NA

NA

NA

0

0

0

3

4

STARTING:

SHUTTER SETTING

1

10

5

7

10

10

8

6

8

BAND SETTING

1

2

2

0

0.5

6

1

6

4

DRAFT OVER FIRE

(in w.c.)

MAX. SMOKE

(bacharach scale)

FLUE CO2 (%)

MIN.

11.0

11.0

11.0

11.0

11.0

11.0

11.0

11.0

11.0

MAX

12.5

12.5

12.5

12.5

12.5

12.5

12.5

12.5

12.5

#1

-0.02

-0.02

#1

#1

#1

#1

#1

#1

#1

#1

-0.02

-0.02

-0.02

-0.02

-0.02

-0.02

-0.02

NONE

NONE

NONE

NONE

NONE

NONE

NONE

STATIC PLATE

LOW FIRING RATE

BAFFLE

BECKETT

#3708

BECKETT

#3708

BOILER MODEL

WARNING

ATTEMPTS TO USE BURNERS OR BURNER CONFIGURATIONS OTHER THAN

THOSE SHOWN IN TABLE 3 COULD RESULT IN RELIABILITY PROBLEMS,
PROPERTY DAMAGE OR UNSAFE OPERATION.

Advertising
This manual is related to the following products: