Iii before installing – Crown Boiler TWZ175 User Manual

Page 5

Advertising
background image

3

taBlE 1a: GEnEral sPEcIFIcatIOns

Notes:

1. Net Ratings are based on piping and pick-up allowances of 1.15.
2. Burner Capacity Rating, GPH is based on #2 oil with a Gross

Heating Value equal to 140000 BTU/Gal.

3. Maximum Working Pressure, Water - 50 PSI.
4. Tankless Heater Ratings based on I=W=H test standard.

III Before Installing

1) Safe, reliable operation of this boiler depends upon installation by a professional heating contractor in strict accordance

with this manual and the requirements of the authority having jurisdiction.

In the absence of an authority having jurisdiction, installation must be in accordance with this manual and the latest

edition of Installation of Oil Burning Equipment (ANSI/NFPA31).

Where required by the authority having jurisdiction, this installation must conform to the latest edition of Standard for

Controls and Safety Devices for Automatically Fired Boilers (ANSI/ASME CSD-1).

2) Make sure that a properly sized chimney is available which is in good condition. Consult the authority having

jurisdiction, Part VI of this manual, and

ANSI/NFPA31 for additional information on venting requirements.

taBlE 1b: OPtIOnal tanKlEss HEatEr ratInGs

Power (“side Wall”) Venting - Important note

Two problems arise when any oil-fired appliance is power vented:

1. There is sometimes an accelerated rate of soot buildup on the oil burner cad-cell, spinner etc.
2. There is a potential for severe damage to the side of the structure in the event that the boiler operates at a high smoke

level. This can happen for many reasons, some of which are out of the control of both the installer and appliance

manufacturer.

Crown Boiler Company recommends the use of a chimney to vent the TWZ series boilers. If a power venter must be used, it

is the responsibility of the installer and power vent manufacturer to “engineer” the power vent system. crOWn BOIlEr

cOMPanY WIll assuME nO rEsPOnsIBIlItY FOr DaMaGE tO sIDInG, Etc. FrOM a POWEr

VEntED OIl-FIrED BOIlEr. tHIs aPPlIEs rEGarDlEss OF tHE causE OF tHE sOOtInG.

"A"

"B"

"C"

TWZ065

3

0.65

80000

70000

86.1

16.0

17-3/8

8 5/16

6

TWZ075

3

0.75

91000

79000

85.8

16.0

17-3/8

8 5/16

6

TWZ100

3

1.00

120000

104000

84.3

16.0

17-3/8

8 5/16

6

TWZ090

4

0.90

111000

97000

86.0

20.0

22-3/8

10 13/16

7

TWZ125

4

1.25

152000

132000

85.1

20.0

22-3/8

10 13/16

7

TWZ150

4

1.50

179000

156000

84.0

20.0

22-3/8

10 13/16

7

TWZ120

5

1.20

147000

128000

86.0

24.0

27-3/8

13 5/16

8

TWZ175

5

1.75

212000

184000

85.1

24.0

27-3/8

13 5/16

8

TWZ200

5

2.00

241000

210000

84.7

24.0

27-3/8

13 5/16

8

I=B=R Net

Rating (Btu/hr) AFUE (%)

Approx.

Water

Content (Gal)

Dimensions (inches)

Boiler Model

Number of

Sections

Burner

Input

(Gal/hr)

DOE Heating

Capacity

(Btu/hr)

TWZ065

TWZ075

TWZ100

TWZ090

TWZ125

TWZ150

TWZ120

TWZ175

TWZ200

Boiler Model

2.75

3.00

3.50

4.25

4.75

Tankless Heater Rating

(Gal/min)

3.25

3.25

3.75

4.00

Advertising