taBlE 3b: carlIn BurnEr cOnFIGuratIOn anD sEtuP Data

BURNER MODEL

EZ-1HP

EZ-1HP

EZ-1HP

EZ-1HP

EZ-1HP

EZ-1HP

EZ-1HP

EZ-2HP

STANDARD

DEL.

HAGO

HAGO

DEL.

DEL.

HAGO

HAGO

DEL.

NOZZLE

0.55/70B 0.60/60ES 0.85/60B 0.75/60A 1.00/60A 1.25/60B 1.00/60B

1.50/60A

PUMP PRESS (psi)

150

150

150

150

150

150

150

150

HEAD BAR

0.50

0.60-0.65 0.85-1.00

0.75

0.85-1.00 1.10-1.25 0.85-1.00

1.50

STARTING

BAND SETTING

0.55

0.60

0.75

0.75

1.00-1.10 1.25-1.35

0.90

1.75

DRAFT OVER FIRE

(in w.c.)

MAX. SMOKE

(bacharach scale)

FLUE CO2 (%)

MIN.

11.0

11.0

11.0

11.0

11.0

11.0

11.0

11.0

MAX

12.5

12.5

12.5

12.5

12.5

12.5

12.5

12.5

TWZ125 TWZ150 TWZ120 TWZ175 TWZ200

-0.02

-0.02

-0.02

-0.02

BOILER MODEL

TWZ065 TWZ075 TWZ100 TWZ090

#1

#1

#1

-0.02

-0.02

-0.02

-0.02

#1

#1

#1

#1

#1

taBlE 3c: rIEllO BurnEr cOnFIGuratIOn anD sEtuP Data

BURNER MODEL

40F5

40F5

40F5

40F10

40F10

40F10

STANDARD

DEL

DEL

DEL.

DEL

HAGO

DEL

NOZZLE

0.60/60A 0.85/60W

1.00/60A 1.25/60B

1.35/45B 1.65/45B

PUMP PRESS (psi)

150

150

150

150

150

150

TURBULATOR

0

2

4

1

1.5

2

AIR

SHUTTER SETTING

2.60

2.85

4

3

3

3.8

DRAFT OVER FIRE

(in w.c.)

MAX. SMOKE

(bacharach scale)

FLUE CO2 (%)

MIN.

11.0

11.0

11.0

11.0

11.0

11.0

MAX

12.5

12.5

12.5

12.5

12.5

12.5

TWZ150

TWZ120

TWZ175

TWZ200

BOILER MODEL

TWZ065

TWZ075

TWZ100

TWZ090

TWZ125

-0.02

#1

#1

#1

#1

#1

#1

-0.02

-0.02

-0.02

-0.02

-0.02

XII service and Maintenance

The following procedure should be performed on an annual basis:
1) Turn off electrical power and oil supply to the boiler.
2) Clean the boiler as follows:

a) Remove vent connector and piping.

b) Remove barometric draft regulator.

c) Remove top jacket panel to gain access to boiler flue collector.

d) Unscrew four wing nuts and remove canopy retaining carriage bolts, lift off the canopy and ceramic fiber sealing

strips.

e) Unplug the burner, disconnect the oil lines (if the pump is hard piped), and remove the two 5/16” bolts securing the

burner door. Open the burner swing door.