Carrier 30HXA,HXC076-186 Water-Cooled and Condenserless Chillers User Manual

Page 11

Advertising
background image

30HXA REFRIGERANT PIPING (See Fig. 7) — Take
care when running the refrigerant piping from the 30HXA
unit to the remote condenser(s) to avoid excessive pres-
sure drops. The pressure drop using R-134a refrigerant is
different than when using R-22 refrigerant. See Tables 2 and
3 for an example for a 2 F (1.1 C) pressure drop in saturated
temperature in the discharge (hot gas) line and liquid line,
respectively. Refer to Fig. 9 and 10 for line sizing informa-
tion for the discharge and liquid lines for 30HXA (R-134a)
units.

Table 2 — Discharge Line 2 F (1.1 C) Drop in

Saturated Temperature Example

SATURATED
DISCHARGE

TEMP

PRESSURE

R-134a

R-22

F

C

Psig

kPa

Psig

kPa

126

52.2

187.5

1293

281.6

1942

124

51.1

182.0

1255

274.3

1891

PRESSURE

5.5

38

7.3

51

PRESSURE
RELIEF

DISCHARGE
LINE

LIQUID LINE

LIQUID LINE

ANGLE
VALVE

OIL
SEPARATOR

COOLER*

TO REMOTE
CONDENSER(S)

TO REMOTE
CONDENSER(S)

TO REMOTE
CONDENSER(S)

TO REMOTE
CONDENSER(S)

EXV

EXV

Fig. 7 — Typical 30HXA Refrigerant Piping to Remote Condenser

NOTES:
1. Piping shown is for general point-of-connection only and is not in-

tended to show details for a specific installation. Certified field wir-
ing and dimensional drawings are available upon request. The 30HXA
units should be installed using certified drawings.

2. Refer to Carrier System Design Manual for details regarding pip-

ing techniques.

3. Piping and pressure relief devices are field supplied.
4. Vent pipes properly per local codes.

LEGEND

EXV — Electronic Expansion Valve

*See Fig. 6 for typical cooler piping.

LEGEND

COM — Common
N.O.

Normally Open

Fig. 8 — Differential Flow Switch

11

Advertising