Carrier 30HXA,HXC076-186 Water-Cooled and Condenserless Chillers User Manual

Page 21

Advertising
background image

Table 5A — Compressor Electrical Data, 30HXC Units (cont)

UNIT SIZE

30HXC

NAMEPLATE

V-Hz

(3 Phase)

COMPRESSOR NUMBERS

A1

B1

RLA

LRA

RLA

LRA

186

208/230-60

*

*

*

*

460-60

103.1

685

103.1

685

575-60

82.4

548

82.4

548

380-60

124.8

757

124.8

757

230-50

*

*

*

*

346-50

*

*

*

*

380/415-50

128.6

856

128.6

856

186-WD

208/230-60

228.8

433

228.8

433

460-60

103.1

216

103.1

216

575-60

82.4

173

82.4

173

380-60

124.8

239

124.8

239

230-50

212.5

432

212.5

432

346-50

141.0

297

141.0

297

380/415-50

128.6

270

128.6

270

LEGEND

LRA — Locked Rotor Amps
RLA — Rated Load Amps
WD

Wye-Delta Start

*Units are shipped with wye-delta start as standard. Across-the-line start is not available.

21