Carrier 30HXA,HXC076-186 Water-Cooled and Condenserless Chillers User Manual

Page 18

Advertising
background image

Table 4B — Unit Electrical Data, 30HXA Units* (cont)

UNIT

30HXA

VOLTAGE

POWER CIRCUIT

CONTROL CIRCUIT

ICF

Nameplate

(3 Ph)

Supplied

Min

Max

MCA

MOCP

Recommended

Fuse Size

Voltage

(Single

Ph)

Min

Max

MCA

MOCP

WD

XL

161

208/230-60

187

253

437/295

700/500

600/400

115-60

104

127

15

15

979

460-60

414

506

304

450

350

115-60

104

127

478

1282

575-60

518

633

243

350

300

115-60

104

127

382

1025

380-60

342

418

368

500

450

230-60

207

254

539

1428

230-50

207

253

415/275

700/450

500/350

230-50

198

254

858

346-50

325

380

276/183

450/300

350/225

230-50

198

254

535

380/415-50

342

440

385

500

450

230-50

198

254

533

1398

171

208/230-60

187

253

359/437

600/700

450/600

115-60

104

127

15

15

1030

460-60

414

506

327

450

400

115-60

104

127

501

1305

575-60

518

633

261

350

300

115-60

104

127

401

1044

380-60

342

418

396

500

450

230-60

207

254

567

1456

230-50

207

253

334/415

600/700

450/500

230-50

198

254

905

346-50

325

380

222/276

350/450

300/350

230-50

198

254

616

380/415-50

342

440

413

600

500

230-50

198

254

562

1427

186

208/230-60

187

253

437/437

700/700

600/600

115-60

104

127

15

15

1093

460-60

414

506

355

500

400

115-60

104

127

529

1333

575-60

518

633

284

400

350

115-60

104

127

539

1066

380-60

342

418

239/239

400/400

300/300

230-60

207

254

601

1490

230-50

207

253

415/415

700/700

500/500

230-50

198

254

970

346-50

325

380

276/276

450/450

350/350

230-50

198

254

660

380/415-50

342

440

453

600

600

230-50

198

254

601

1466

LEGEND

ICF

Maximum Instantaneous Current Flow during start-up

(the point in the starting sequence where the sum of the
LRA for the start-up compressor, plus the total RLA for
all running compressors, plus the total FLA for all run-
ning fan motors is at a maximum)

MCA

Minimum Circuit Ampacity (for wire sizing)

MOCP — Maximum Overcurrent Protection
RLA

Rated Load Amps

WD

Wye-Delta Start

XL

Across-the-Line Start

*Refer to Carrier’s electronic catalog for the most current electrical

data.

†Wye-Delta Start is standard. Not available in across-the-line start.

**The 30HX186 units have 2 terminal blocks/non-fused disconnects

and 6 parallel conductors/non-fused disconnects.

††The 30HXA136-186 units have 2 terminal blocks/non-fused

disconnects and 6 parallel conductors/non-fused disconnects.

NOTES:
1. Main power must be supplied from a field-supplied fused electri-

cal service with a (factory- or field-installed) disconnect located in
sight from the unit.

2. Control circuit power must be supplied from a separate source through

a field-supplied disconnect. The control circuit accessory trans-
former may be applied to power from the main unit power supply.

3. Maximum incoming wire size for each terminal block is 500 kcmil.
4. Maximum allowable phase imbalance is: voltage, 2%; amps, 5%.
5. Units with one MCA value have one main terminal block. Units

with 2 MCA values require multiple conductors.

6. Use copper conductors only.

7. The MOCP is calculated as follows:

MOCP = (2.25) (largest RLA) + the sum of the other RLAs. Size
the fuse one size down from the result. The RLAs are listed on the
unit nameplate.
The recommended fuse size in amps (RFA) is calculated as
follows:
RFA = (1.50) (largest RLA) + the sum of the other RLAs. Size
the fuse one size up from the result. The RLAs are listed on the
unit nameplate.

8. Units have the following power wiring terminal blocks and parallel

conductors:

VOLTAGE

TERMINAL

BLOCKS

OR NON-FUSED

DISCONNECTS

PARALLEL

CONDUCTORS

OR NON-FUSED

DISCONNECTS

208/230

2

6

460

1

3

575

1

3

380**

1

3

230

2

6

346††

1

3

380/415

1

3

18