Carrier 30HXA,HXC076-186 Water-Cooled and Condenserless Chillers User Manual

Page 25

Advertising
background image

LEGEND

ALM

Alarm

CCN

Carrier Comfort Network

COMM

Communications

CWFS

Chilled Water (Fluid) Flow Switch

CWP

Chilled Water (Fluid) Pump

CWPI

Chilled Water (Fluid) Pump Interlock

EQUIP

Equipment

GND, GRD — Ground
NEC

National Electrical Code (U.S.A.)

TB

Terminal Block

Field Power Wiring
Field Control Wiring
Factory-Installed Wiring

NOTES:
1. Factory wiring is in accordance with NEC. Field modifications or additions must be in compliance with all appli-

cable codes.

2. Wiring for main field supply must be rated 75° C minimum. Use copper for all units. Maximum incoming wire size

for each terminal block is 500 kcmil.

3. Power for control circuit should be supplied from a separate source through a field-supplied, fused disconnect with

15 amp maximum protection for all control circuits. Connect control circuit power to terminals 1 and 2 of TB4.
Connect neutral side of supply to terminal 2 of TB4. Control circuit conductors for all units must be copper only.

4. Terminals 13 and 14 of TB2 are for field external connection for remote on-off. The contacts must be rated for dry

circuit application capable of handling a 24 vac to 50 mA load. Remove jumper between 13 and 14 of TB2 if remote
on-off is installed.

5. Terminals 11 and 12 of TB2 are for chilled water flow switch (CWFS) and chilled water pump interlock (CWPI)

functions. The contacts must be rated for dry circuit application capable of handling a 24 vac to 50 mA load.

6. Terminals 4 and 5 of TB2 are for control of chilled water pump starter. The maximum load allowed for the chilled

water pump relay is 125 va sealed, 1250 va inrush.

7. Terminals 2 and 3 of TB2 are for alarm. The maximum load allowed for the alarm is 125 va sealed, 1250 va inrush.

Fig. 13 — Field Control Wiring

25