Carrier 30HXA,HXC076-186 Water-Cooled and Condenserless Chillers User Manual

Page 16

Advertising
background image

Table 4A — Unit Electrical Data, 30HXC Units* (cont)

UNIT

30HXC

VOLTAGE

POWER CIRCUIT

CONTROL CIRCUIT

ICF

Nameplate

(3 Ph)

Supplied

Min

Max

MCA

MOCP

Recommended

Fuse Size

Voltage

(Single

Ph)

Min

Max

MCA

MOCP

WD

XL

161

208/230-60

187

253

285/197

500/350

350/250

115-60

104

127

15

15

591

460-60

414

506

200

300

250

115-60

104

127

287

756

575-60

518

633

160

225

200

115-60

104

127

230

605

380-60

342

418

242

350

300

230-60

207

254

325

843

230-50

207

253

266/182

450/300

350/225

230-50

198

254

578

346-50

325

380

273

400

350

230-50

198

254

394

380/415-50

342

440

249

350

300

230-50

198

254

358

944

171

208/230-60

187

253

238/285

400/500

300/400

115-60

104

127

15

15

624

460-60

414

506

215

300

250

115-60

104

127

302

771

575-60

518

633

172

250

200

115-60

104

127

242

617

380-60

342

418

260

350

300

230-60

207

254

343

861

230-50

207

253

219/266

350/450

300/350

230-50

198

254

607

346-50

325

380

145/176

250/300

175/225

230-50

198

254

413

380/415-50

342

440

267

350

300

230-50

198

254

376

962

186

208/230-60

187

253

285/285

500/500

400/400

115-60

104

127

15

15

661

460-60

414

506

232

300

300

115-60

104

127

319

788

575-60

518

633

185

250

225

115-60

104

127

255

630

380-60

342

418

156/156

250/250

200/200

230-60

207

254

364

882

230-50

207

253

266/266

450/450

350/350

230-50

198

254

645

346-50

325

380

176/176

300/300

225/225

230-50

198

254

438

380/415-50

342

440

289

400

350

230-50

198

254

399

985

LEGEND

ICF

Maximum Instantaneous Current Flow during start-up

(the point in the starting sequence where the sum of the
LRA for the start-up compressor, plus the total RLA for
all running compressors, plus the total FLA for all run-
ning fan motors is at a maximum)

MCA

Minimum Circuit Ampacity (for wire sizing)

MOCP — Maximum Overcurrent Protection
RLA

Rated Load Amps

WD

Wye-Delta Start

XL

Across-the-Line Start

*Refer to Carrier’s electronic catalog for the most current electrical

data.

†Wye-Delta Start is standard. Not available in across-the-line start.

**The 30HX186 units have 2 terminal blocks/non-fused disconnects

and 6 parallel conductors/non-fused disconnects.

††The 30HXC171 and 186 units have 2 terminal blocks/non-fused

disconnects and 6 parallel conductors/non-fused disconnects.

NOTES:
1. Main power must be supplied from a field-supplied fused electri-

cal service with a (factory- or field-installed) disconnect located in
sight from the unit.

2. Control circuit power must be supplied from a separate source through

a field-supplied disconnect. The control circuit accessory trans-
former may be applied to power from the main unit power supply.

3. Maximum incoming wire size for each terminal block is 500 kcmil.
4. Maximum allowable phase imbalance is: voltage, 2%; amps, 5%.
5. Units with one MCA value have one main terminal block. Units

with 2 MCA values require multiple conductors.

6. Use copper conductors only.

7. The MOCP is calculated as follows:

MOCP = (2.25) (largest RLA) + the sum of the other RLAs. Size
the fuse one size down from the result. The RLAs are listed on the
unit nameplate.
The recommended fuse size in amps (RFA) is calculated as
follows:
RFA = (1.50) (largest RLA) + the sum of the other RLAs. Size
the fuse one size up from the result. The RLAs are listed on the
unit nameplate.

8. Units have the following power wiring terminal blocks and parallel

conductors:

VOLTAGE

TERMINAL

BLOCKS

OR NON-FUSED

DISCONNECTS

PARALLEL

CONDUCTORS

OR NON-FUSED

DISCONNECTS

208/230

2

6

460

1

3

575

1

3

380**

1

3

230

2

6

346††

1

3

380/415

1

3

16