Table 5B — Compressor Electrical Data, 30HXA Units (cont)

UNIT SIZE

30HXA

NAMEPLATE

V-Hz

(3 Phase)

COMPRESSOR NUMBERS

A1

B1

RLA

LRA

RLA

LRA

186

208/230-60

*

*

*

*

460-60

157.9

1175

157.9

1175

575-60

126.2

940

126.2

940

380-60

191.2

1299

191.2

1299

230-50

*

*

*

*

346-50

*

*

*

*

380/415-50

201.2

1265

201.2

1265

186-WD

208/230-60

349.6

743

349.6

743

460-60

157.9

371

157.9

371

575-60

126.2

297

126.2

297

380-60

191.2

410

191.2

410

230-50

332.3

638

332.3

638

346-50

220.5

439

220.5

439

380/415-50

201.2

400

201.2

400

LEGEND

LRA — Locked Rotor Amps
RLA — Rated Load Amps
WD

Wye-Delta Start

*Units are shipped with wye-delta start as standard. Across-the-line start is not available.

LEGEND

EQUIP

Equipment

NEC

National Electrical Code (U.S.A.)

TB

Terminal Block

Y-Delta — Wye-Delta Start
XL

Across-the-Line Start

Field Power Wiring
Field Control Wiring
Factory-Installed Wiring

Fig. 12 — Field Power Wiring

NOTES:
1. Factory wiring is in accordance with NEC. Field modifications or

additions must be in compliance with all applicable codes.

2. Wiring for main field supply must be rated 75° C minimum. Use

copper for all units. Maximum incoming wire size for each terminal
block is 500 kcmil.