Troubleshooting guide – Carrier SERIES 131 58PAV User Manual

Page 10

Advertising
background image

Close door switch and go to start.

Is circuit breaker closed?

Is red LED status light on?

Is red LED status light blinking

rapidly without a pause?

Is door switch closed?

Is there 115v going to switch?

Replace control board.

Replace door switch.

Is red LED status light blinking

ON/OFF slowly with a

combination of short and long

flashes?

Check for correct line voltage

polarity. If units are twinned,

check for proper low-voltage

(24v) transformer phasing.

Check for previous fault by

momentarily shorting the TEST

terminal and the "C" terminal until

the LED goes out. LED will flash

the status code of any previous

fault or the code 11 (ONE

SHORT AND ONE LONG

FLASH) if no previous fault. After

the control repeats the code 3

times, it will sequentially operate

inducer motor, HSI, blower motor

relay heat speed, and cool speed

for approximately 10 - 15 sec,

then go off.

Determine status code. The

status code is a 2 digit number

with the first digit determined by

the number of short flashes and

the second digit by the number of

long flashes.

Once status code is determined,

the control will go through a brief

component test sequence by

operating inducer motor, HSI,

blower motor relay heat speed,

and cool speed for approximately

10-15 sec, then go off.

Was there a previous fault code

other than No. 11?

Run system through a heating or

cooling cycle to check operation.

Status codes are erased after 48

hrs or whenever power (115v

or 24v) is interrupted.

Go to section with status code

determined.

Is there 115v at L1 and L2?

NO

NO

NO

NO

NO

YES

YES

YES

YES

YES

NO

NO

YES

YES

YES

START

Is there 24v at SEC-1 and SEC-2?

NO

TROUBLESHOOTING GUIDE

Replace transformer.

Close circuit breaker and

go back to start.

NO

Check for continuity in wire from

circuit breaker to furnace.

YES

10

Advertising