Compaq R6000 User Manual

Page 34

Advertising
background image

Installation

2-9

Connecting the Compaq R6000 UPS

to AC Branch Circuit

High Leakage Current

WARNING: To avoid the risk of electric shock due to high leakage current, earth

connection (grounding) is essential before connecting the unit to an AC supply.
Make sure AC Mains are turned off at the service panel before wiring the
Compaq R6000 UPS.

HIGH LEAKAGE CURRENT

EARTH CONNECTION ESSENTIAL BEFORE CONNECTING SUPPLY

Risk of Fire Notice

WARNING: To reduce the risk of fire, connect the Compaq R6000 UPS only to a
circuit provided with 40 A maximum branch circuit rated overcurrent protection
device in accordance with the National Electrical Code (NFPA 70) and Canadian
Electrical Code, C22.1.

Electrical Safety

WARNING: To reduce the risk of electrical shock or personal injury while

performing this procedure, use a Lockout/Tagout procedure to isolate the
Compaq R6000 UPS from the AC Branch Circuit (AC Mains). The Lockout/Tagout
procedure should conform to local occupational health and safety regulations for
the facility.

Requirements

The Compaq R6000 UPS requires a dedicated branch circuit meeting the
following requirements:

40 Amp circuit with overcurrent protection

An appropriate and readily accessible disconnect device incorporated in
the fixed wiring

200-240 V

single phase

50-60 Hz