Troubleshooting

6-3

Shutdown within 30 seconds Audible Alarm

Table 6-3

Shutdown within 30 seconds Audible Alarm

Audible Alarm Group

Audible Alarm Sound

Cause(s)

Action

Shutdown within 30
seconds

Accelerated beeping.
Begins slowly, and gains

speed as the UPS
approaches shutdown.

UPS shuts down 30 sec
after audible alarm
begins.

Over-temperature.

Check the ambient
temperature in the

room. Refer to Appendix
C, “Environmental
Specifications”

If the ambient
temperature is within

range and the over
temperature alarm is
chronic, contact an
authorized service
provider.

Overload.

Reduce the load. See
section “Connecting
Loads” in Chapter 2

Low battery.

Check the LCD display

(Meters, Battery Volts)

If a shutdown delay has
been programmed, the
accelerated alarm begins
before the last segment
shutoff.

No action needed.

Occurs during the last

minute of sleep timer if
the Sleep mode is
enabled.

No action needed.