Compaq R6000 User Manual

Page 64

Advertising
background image

Configuration

4-9

Enter button to step through the list of alarm descriptions. If more than 1
alarm was indicated, make sure to look at every alarm.

The alarms generated by this UPS are:

Input AC Over Voltage

If the utility voltage rises over the specified range, the UPS will buck the
output voltage down, and trigger a red LED alarm signal. An audible alarm
will be triggered when overvoltage reaches 120% of the nominal range setting.

X Alarms

Input AC Over Voltage

Input AC Under Voltage

If the utility voltage falls below the specified range (20% or more under
voltage), the UPS will boost the output voltage up and raise an alarm. This
alarm will not appear until the UPS is on battery.

X Alarms

Input AC Under Voltage

Input Over or Under Frequency

If the utility frequency suddenly changes, the UPS will raise an alarm. This
only occurs when the UPS goes on battery.

X Alarms

Input Over or Under Frequency

Output Overload

If there are too many loads draining the UPS, the UPS will raise an alarm.
Decrease the number of active devices attached to the UPS outputs.

X Alarms

Output Overload