4a.2 cold water make-up — boiler, 4a.3 water flow requirements — boiler, Laars heating systems – LAARS Pennant PNCV (Sizes 200, 300, 400) - Install and Operating Manual User Manual

Page 19

Advertising
background image

LAARS Heating Systems

Page 18

Pennant 200, 300, 400

Page 19

Figure 8. Hydronic Piping — Primary-Secondary, Reverse-Return, Low Temperature.

CAUTION: THIS DRAWING SHOWS SUGGESTED

PIPING CONFIGURATION AND VALVING, CHECK

WITH LOCAL CODES AND ORDINANCES FOR

ADDITIONAL REQUIREMENTS.

PRIMARY/SECONDARY MANDATORY FOR ALL

VARIABLE FLOW SYSTEMS
INSTALL AIR VENTS AT HIGH POINTS IN SYSTEM
PIPING & SIZING OF EXPANSION TANK

PER TANK MANUFACTURER'S INSTRUCTIONS
DIMENSION "C" (COMMON PIPING) TO BE FOUR

PIPE DIAMETERS, MAX. (NO ELBOWS OR VALVES)

BOILER CIRCUIT PIPING MUST BE EQUAL

TO BOILER WATER CONNECTION SIZE
BOILER CIRC. PUMP SIZED FOR FLOW THROUGH BOILER
DOTTED DEVICES INDICATE ALTERNATE LOCATIONS
PUT BOILER CONTROL SENSOR IN THE SYSTEM

SUPPLY WHEN USING THIS PIPING STYLE.
MINIMUM BOILER INLET WATER TEMPERATURE

MUST BE AT LEAST 120°F.

C

SYSTEM PUMP

MAKE-UP

COLD WATER

SUPPLY

SYSTEM

PUMP LOCATION FOR

PUMP-MOUNTED UNITS

RETURN

SYSTEM

T1

T1

A

B

A

B

ADJUSTMENT PROCEDURE TO MAINTAIN

120°F INLET TEMP:

1. Turn on boiler and open valves A & B.

2. After steady-state operation, if T1 is less than

120°F, slowly close valve B until T1 climbs to

120°F.

3. If T1 is greater than 120°F, slowly close valve

A until T1 drops to 120°F.

4. Check after system operating temperature has

stabilized. Make final adjustments.

CHECK VALVE

TEMPERATURE

SENSOR

VALVE

PURGE VALVE

THERMOMETER

GLOBE VALVE

EXPANSION TANK

WITH AIR SCOOP AND

AUTO AIR VENT

PUMP

PRESSURE REDUCING VALVE

W/ FAST FILL BYPASS

3-WAY VALVE

Model

(Size)

20°F

25°F

30°F

35°F

flow

gpm

H/L

feet

flow

gpm

H/L

feet

flow

gpm

H/L

feet

flow

gpm

H/L

feet

200

17

1.6

14

1.0

11

0.7

10

0.5

300

26

3.5

20

2.3

17

1.6

15

1.2

400

34

6.3

27

4.0

23

2.8

19

2.1

Metric Equivalent
Model

(Size)

11°C

14°C

17°C

19°C

flow

lpm

H/L

m

flow

lpm

H/L

m

flow

lpm

H/L

m

flow

lpm

H/L

m

200

64

0.5

51

0.3

43

0.2

37

0.2

300

97

1.1

77

0.7

64

0.5

55

0.4

400

129

1.9

103

1.2

86

0.9

74

0.6

Notes: gpm = gallons per minute, lpm = liters per minute,

H/L = head loss, ft = head loss in feet,

m = head loss in meters.

Maximum temperature rise is 35°F (19°C), as shown.

Head loss is for boiler’s heat exchanger only.

N/R = not recommended.

Table 8. Water Flow Requirements - PNCH.

4A.2 Cold Water Make-Up — Boiler

1. Connect the cold water supply to the inlet

connection of an automatic fill valve.

2. Install a suitable back flow preventer between the

automatic fill valve and the cold water supply.

3. Install shut off valves where required.

NOTE: The boiler, when used in connection with a

refrigeration system, must be installed so the chilled

medium is piped in parallel with the boiler with

appropriate valves to prevent the chilled medium

from entering the boiler.

The boiler piping system of a hot water heating

boiler connected to heating coils located in air

handling appliances where they may be exposed to

refrigerated air circulation must be equipped with flow

control valves or other automatic means to prevent

gravity circulation of the boiler water during the

cooling cycle.

A boiler installed above radiation level, or as

required by the authority having jurisdiction, must be

provided with a low water cutoff device either as a part

of the boiler or at the time of boiler installation.

4A.3 Water Flow Requirements — Boiler

A hydronic heating (closed loop) application

recirculates the same fluid in the piping system. As a

result, no new minerals or oxygen are introduced into

the system. To ensure a proper operating temperature

leading to long boiler life, a flow rate has been

established based on the fluid temperature rise for this

specific size boiler.

Pump-mounted boilers can be ordered for use in

primary secondary piping systems. The pumps used

are sized for the head loss through the heater, plus 30

feet (9.1 m) of full-sized piping (same size as boiler

outlet) and a normal number of fittings.